Read Panasonic WH-SDC09F3E8 / WH-SDC12F9E8 / WH-SDC14F9E8 / WH-SDC16F9E8 / WH-UD09FE8 / WH-UD12FE8 / WH-UD14FE8 / WH-UD16FE8 Service Manual online
124
17.5.7 Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to
determine water flow error.
determine water flow error.
Malfunction Caused:
1 Faulty water pump.
2 Water leak in system.
3 Faulty connector connection.
4 Faulty water flow switch.
5 Faulty indoor unit PCB (main).
2 Water leak in system.
3 Faulty connector connection.
4 Faulty water flow switch.
5 Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).