17.5.4  Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) 
Malfunction Decision Conditions: 
During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid 
temperature sensor are used to determine sensor error. 
 
Malfunction Caused: 
1  Faulty connector connection. 
2  Faulty sensor. 
3  Faulty indoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 seconds. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 