17.5.5  Service Valve Error (H27) 
Malfunction Decision Conditions: 
During cooling operation, when:- 
[a] Indoor refrigerant pipe temperature at compressor startup - present indoor refrigerant pipe temperature < 2°C 
[b] Present high pressure - high pressure at compressor startup < 5kg/cm
2
 
**Judgment only for first time cooling operation and not during pump down operation. 
 
Malfunction Caused: 
1  3 way valves closed. 
2  Faulty high pressure sensor. 
3  Faulty indoor refrigerant pipe temperature sensor 
4  Faulty outdoor unit PCB (main). 
 
Abnormality Judgment: 
Continue for 5 minutes. 
 
 
 