117
Diagnosis display
Abnormality/Protection control
Abnormality judgement
Primary location to verify
F36
Outdoor air temperature sensor
abnormality
abnormality
Continue for 5 sec.
Outdoor air temperature sensor
(defective or disconnected)
F37
Indoor water inlet temperature sensor
abnormality
abnormality
Continue for 5 sec.
Water inlet temperature sensor
(defective or disconnected)
F40
Outdoor discharge pipe temperature
sensor abnormality
sensor abnormality
Continue for 5 sec.
Outdoor discharge pipe temperature
sensor (defective or disconnected)
F41
PFC control
4 times occurrence within 10
minutes
minutes
Voltage at PFC
F42
Outdoor heat exchanger temperature
sensor abnormality
sensor abnormality
Continue for 5 sec.
Outdoor heat exchanger temperature
sensor (defective or disconnected)
F43
Outdoor defrost sensor abnormality
Continue for 5 sec.
Outdoor defrost sensor (defective or
disconnected)
F45
Indoor water outlet temperature sensor
abnormality
abnormality
Continue for 5 sec.
Water outlet temperature sensor
(defective or disconnected)
F46
Outdoor Current Transformer open
circuit
circuit
—
Insufficient refrigerant
Outdoor PCB
Outdoor PCB
Compressor low
F48
Outdoor EVA outlet temperature sensor
abnormality
abnormality
Continue for 5 sec.
Outdoor EVA outlet temperature sensor
(defective or disconnected)
F49
Outdoor bypass outlet temperature
sensor abnormality
sensor abnormality
Continue for 5 sec.
Outdoor bypass outlet temperature
sensor (defective or disconnected)
F95
Cooling high pressure overload
protection
protection
—
Outdoor high pressure sensor
Water pump or water leakage
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB
Outdoor PCB