WH-ADC0916H9E8, WH-UD09HE8, WH-UD12HE8, WH-UD16HE8, WH-UX09HE8, WH-UX12HE8, WH-UX16HE8, WH-UQ09HE8, WH-UQ12HE8, WH-UQ16HE8 - Panasonic Air Conditioner Service Manual (repair manual). Page 119

Read Panasonic WH-ADC0916H9E8 / WH-UD09HE8 / WH-UD12HE8 / WH-UD16HE8 / WH-UX09HE8 / WH-UX12HE8 / WH-UX16HE8 / WH-UQ09HE8 / WH-UQ12HE8 / WH-UQ16HE8 Service Manual online

119 
12.1.5  High Pressure Sensor Control 
 Purpose: 
- To protect the system operation. 
 Detection 
period: 
- After compressor on for 1 minute. 
 Detection 
conditions: 
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously. 
 After 
detection: 
- When abnormality is detected 4 times within 120 minutes, unit stop operation. 
- OFF/ON control panel LED will blink (H64 error occurs). 
12.1.6  Outside Temperature Current Control 
 
 
12.1.7  Crank Case Heater Control 
 Purpose: 
- For compressor protection during low outdoor ambient operation (during heating low temperature operation). 
 Control 
content: 
a.  Trigger heater START condition 
When the outdoor air temperature is below than 5°C, and discharge temperature is 11°C or below. 
b.  Resetting heater STOP condition 
1. 
When the outdoor air temperature exceeds entry condition (2°C) 
2. 
When the discharge temperature exceeds entry condition (5°C) 
12.1.8  Compressor Cold Start Prohibition Control 
 Purpose: 
- Protect compressor when poor compressor oil return at low outdoor ambient and high water temperature 
  condition. 
 Control 
content: 
- Do not run compressor when below condition fulfilled 
a.  Compressor top temperature < 10°C 
b.  Outdoor ambient < -20°C 
c.  Water temperature > 40°C 
Compressor operate with
limited operation
Outdoor temperature
23°C
14°C
-28°C
21°C
-30°C
12°C
Max.
current
value is
regulated
Page of 127