Remote control setting 
 
For this function, following items need to be set on R/C (installer menu) – 
 
  SG control = YES or NO 
  Capacity up setting 1 
o  Heating capacity [50 ~ 150 %] 
o  DHW capacity [50 ~ 150 %] 
  Capacity up setting 2 
o  Heating capacity [50 ~ 150 %] 
o  DHW capacity [50 ~ 150 %] 
 
Control contents: 
 
If SG control on remote control = "Yes", then following control only activate by digital input. 
 
  While Digital input is " 00 " (Normal operation) 
o  Normal operation. Once detect '00' system will operate back to normal condition. 
(All the target set temperature for heating side and DHW side will return back to previous set temperature 
when digital signal change from "10' or"11" back to "00".) 
  While digital input is detected " 01 " (HP stop) 
o  Heat pump & room heater & tank heater cannot operate. 
(Solar control and Boiler back up and 2 Zone control can activate.) 
  While digital input is detected " 10 " (Capacity 1) 
o  Target temperature for heating and DHW Tank is changed according to the percentage set by Remote 
control setting. However, which setting temperature is change depend on system setting. 
  While digital input is detected " 11 " (Capacity 2) 
o  Target temperature for heating and DHW Tank is changed according to the percentage set by Remote 
control setting. However, which setting temperature is change depend on system setting. 
  While digital input is detected " 10 " (Capacity 1) 
o  Setting temperature for heating and Tank is changed. 
However, which setting temperature is change depend on system setting. 
 
If Buffer selection is “YES” 
Room side 
New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting  
(" capacity 1) % 
* Max Min regulation is follow Target Buffer tank temperature control specification 
** No change of Target zone water temperature, only set higher buffer tank temperature. 
 
DHW Tank side 
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 1) % *  
(Max regulation depend on the tank max setting limit) 
 
If Buffer selection is “NO” 
Room side 
New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting 
(*Capacity 1) % 
(Zone 1 and Zone 2 will change according to its own target zone water temperature.) 
(Max regulation depend on the temperature control type select) 
 
DHW Tank side 
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 1) % 
* (Max regulation depends on the tank max setting limit) 
 
  While digital input is detected " 11 " (Capacity 2) 
o  Setting temperature for heating and Tank is changed. 
However, which setting temperature is change depend on system setting. 
 
 
 
 
 
 