If Buffer selection is “YES” 
Room side 
New Target Buffer tank temperature = Current Target Buffer Tank Temperature * Remote Control setting  
(" capacity 2) % 
* Max Min regulation is follow Target Buffer tank temperature control specification 
** No change of Target zone water temperature, only set higher buffer tank temperature. 
 
DHW Tank side 
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) % 
* (Max regulation depends on the tank max setting limit) 
 
If Buffer selection is “NO” 
Room side 
New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting 
(*Capacity 2) % 
(Zone 1 and Zone 2 will change according to it's own target zone water temperature.) 
(Max regulation depend on the temperature control type select) 
 
DHW Tank side 
New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) % 
* (Max regulation depends on the tank max setting limit) 
** This function is not applicable for Cooling mode. 
11.28   Demand Control (Optional PCB) 
Remote control setting: 
  When Optional PCB connection select 'YES", Demand Control function can select "YES" or "NO". 
 
Purpose: 
  After the demand control select YES, below control will activated. 
o 0-10V 
Demand 
control 
 
0-10V Demand control 
  Demand control is use to reduce the current usage of heat pump unit by third party device. 
 
Control start condition: 
  Select “YES” at Demand control at installer menu. 
  0-10V input for this electrical current control is detected. 
 
Control content: 
  If start condition is fulfilled, indoor will receive the voltage signal from optional PCB. Indoor will send the rate 
value to outdoor unit. 
  Outdoor will change the current limit according to the percentage receive from indoor unit. 
11.29   Holiday Mode 
 Purpose: 
Promotes energy saving by allowing the user to stop the system during holiday and enables the system to 
resume at the preset temperature after holiday. 
 
 Control 
details: 
o  Indoor operate the unit according running mode request. Target temperature will follow holiday setting 
temperature. 
  If heat mode request is receive, Target Water Out Temperature will change according to holiday shift 
temperature set. 
[If heat is set OFF at holiday, unit, water pump and zone control will OFF] 
  If tank mode request is receive, Target Tank Set Temperature will change according to the holiday tank 
shift temperature set. 
[If tank is set OFF at holiday, heat pump and tank heater will OFF] 
o  After days of holiday have been set, heat pump will stop and only resume operation at the end of holiday 
countdown. 
 
 Start 
condition: 
o  Holiday timer set and the holiday timer start 
* The day holiday mode was set is counted as day 1. 