13.3  Protection Control for Cooling Operation 
13.3.1  Outdoor Air Temperature Control 
  The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
  This control will begin 1 minute after the compressor starts. 
 Compressor 
frequency will adjust base on outdoor air temperature. 
 
 
13.3.2  Freeze Prevention Control 1 
4  When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will 
stop operating. 
5  Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C. 
6  Indoor heat exchanger freeze prevention (H99) will memory in error history. 
 
 
Limited
frequency
Compressor
stop
Free
25°C
22°C
19°C
16°C