13.  Protection Control (WH-UX09HE8, WH-UX12HE8 and  
    WH-UX16HE8) 
13.1  Protection Control for All Operations 
13.1.1  Time Delay Safety Control 
2  The compressor will not start for three minutes after stop of operation. 
13.1.2  30 Seconds Forced Operation 
3  Once the compressor starts operation, it will not stop its operation for 30 seconds. 
4  However, it can be stopped using control panel at indoor unit. 
13.1.3  Total Running Current Control 
4  When the outdoor running current exceeds X value, the compressor frequency will decrease. 
5  If the outdoor running current does not exceed X value, the compressor frequency will return to normal 
operating frequency. 
6  If the outdoor running current continue to increase till exceed Y value, compressor will stop, and if this occurs 
3 times within 20 minutes, system will stop operation and OFF/ON control panel LED will blink (F16 error 
occurs). 
 
 UX09HE8 
UX12HE8 
UX16HE8 
Operation Mode 
X (A) 
Y (A) 
X (A) 
Y (A) 
X (A) 
Y (A) 
Heating 9.4 
11.8 
10.9 
11.8 
15.5 
16.5 
Cooling 6.2 
11.8 
6.2 
11.8 
7.1 
16.5 
 
B.  DC Peak Current Control 
4  When the current to IPM exceeds set value of 34 A, compressor will stop. Compressor will restart after three 
minutes. 
5  If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart 
after two minutes. 
6  If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after 
one minute. If this condition repeats continuously for seven times, system will stop operation and OFF/ON 
control panel LED will blink (F23 error occurs). 
13.1.4 Compressor Overheating Prevention Control 
  The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in 
below figures. When the compressor tank temperature exceeds 107°C, compressor will stop, and if this occurs 
4 times within 30 minutes, system will stop operation and OFF/ON control panel LED will blink (F20 error occurs). 
 
 
 
 
 
 
 
 
 
 
 
Compressor tank temperature
Compressor = OFF
Compressor
Frequency Reduced
Compressor
Frequency Maintain
Free
108°C
110°C
112°C
97°C
97°C
97°C