S-22KA1E5, S-28KA1E5, S-36KA1E5, S-45KA1E5, S-56KA1E5, S-63KA1E5, S-71KA1E5, S-22YA1E5, S-28YA1E5, S-36YA1E5, S-45YA1E5, S-56YA1E5, S-22NA1E5, S-28NA1E5, S-32NA1E5, S-36NA1E5, S-45NA1E5, S-56NA1E5, S-45MA1E5, S-56MA1E5, S-63MA1E5, S-7 - Panasonic Air Conditioner Service Manual (repair manual). Page 10

Read Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual online

10 
x  Heat / Cool Mode selection 
o  Must use together with Cooling / Heating Selector Switch (CZ-RD1) 
o  With the heat cool selector switch, operation mode (Heat / Cool / Fan) can be set & fixed by higher 
authority user. 
o  If OFF selected, Unit will operate freely base on remote setting. 
o  If ON & FAN selected, Unit will in priority to operate fan mode only. 
o  If ON & MODE & HEAT selected, unit will in priority to operate heat mode only. 
o  Priority mode is indicated in wired remote.  If remote setting is not same mode with Priority Mode, indoor 
unit will standby until priority mode canceled. (power led blinks ON 2.5sec; OFF 0.5sec) 
 
 
 
x  Share External Signals to Next Outdoor Unit 
o  The Cooling / Heating Selector and Forced Stop input signals can be share with next outdoor systems. 
o  Maximum 30 outdoor units can share these signals.  
o  Wire requirement : 0.5mmƳ diameter and maximum length is 100m. 
o  Demand control signal cannot be shared to the next system. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 service manuals if exist.