S-22KA1E5, S-28KA1E5, S-36KA1E5, S-45KA1E5, S-56KA1E5, S-63KA1E5, S-71KA1E5, S-22YA1E5, S-28YA1E5, S-36YA1E5, S-45YA1E5, S-56YA1E5, S-22NA1E5, S-28NA1E5, S-32NA1E5, S-36NA1E5, S-45NA1E5, S-56NA1E5, S-45MA1E5, S-56MA1E5, S-63MA1E5, S-7 - Panasonic Air Conditioner Service Manual (repair manual). Page 9

Read Panasonic S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 Service Manual online

Interface Module for External Control / Integration 
CZ-CAP1 
x Demand 
Control 
With Demand Control, it is possible to limit maximum electrical current to air conditioner. This usually 
used to integrate with central control system, building automation system or etc. 
 
 
From external device, it is required to use a volt free 
contact (relay) for integration.  
(DC24V 2mA, wire length max 150m) 
 
COM shorted with 
Max rated current 
LV1 70% 
LV2 40% 
LV3 0% 
 
x Forced 
Stop 
o  With the Forced Stop input, it is possible to override the air conditioning operation to force stop if signal is 
received from a fire alarm system, BAS or etc. 
 
 
From external device, it is required to use a volt free 
contact (relay) for integration.  
(DC24V 2mA, wire length max 150m) 
 
When contact closed, AC will forced 
and continue stop operation. 
 
When contact opened, AC will switch to standby condition.  
 
LED display on PCB 
2 3 4 5 6 7 8 9 
Ɉ 
Ɉ 
Ɉ 
Ɉ 
Ɉ 
Ɉ 
Ɉ 
Ɉ 
Page of 127
Display

Click on the first or last page to see other S-22KA1E5 / S-28KA1E5 / S-36KA1E5 / S-45KA1E5 / S-56KA1E5 / S-63KA1E5 / S-71KA1E5 / S-22YA1E5 / S-28YA1E5 / S-36YA1E5 / S-45YA1E5 / S-56YA1E5 / S-22NA1E5 / S-28NA1E5 / S-32NA1E5 / S-36NA1E5 / S-45NA1E5 / S-56NA1E5 / S-45MA1E5 / S-56MA1E5 / S-63MA1E5 / S-7 service manuals if exist.