12.13 Sterilization Mode 
Purpose: 
-  To sterilize water tank by setting the required boiling temperature. 
Remote control setting 
-  Days for sterilization function to start can be select. 
-  Time of selected day to start sterilization function. 
-  Boiling temperature (External heater is 55°C ~ 75°C, Internal heater is 55°C ~ 65°C) 
-  Maximum operation time is 5 minutes to 1 hour. 
Start condition 
-  Tank connection set to “YES” by remote control 
-  Sterilization function selects “YES”. 
-  Sterilization signal received from remote controller by timer. 
-  Tank mode request ON. 
Stop condition 
-  When boiling timer is completed. Boiling timer (Remote control set maximum operation time) start counting 
once tank achieve boiling set temperature OR 
-  After 8 hours of operation since sterilization start. 
-  Tank mode request OFF. 
Control content: 
-  During sterilization function activation time, target tank set temperature will internally change to boiling set 
temperature. 
-  During sterilization activates, heat pump and heater (external or internal) will operate as normal tank mode to 
achieve the boiling set temperature. 
-  Sterilization operation will end when stop condition is fulfill. 
-  After sterilization is complete, tank set temperature will resume to normal operation. 
* Tank temperature may not achieve boiling set temperature if tank heater is select OFF OR external compressor 
switch. 
 
 