12.10  Force Heater Mode 
Purpose of Force Heater Mode 
-  As a backup heat source when heat pump error. Force heater Mode control backup heater to heat up the 
room circuit, and turn ON back up heater or booster heater to boil up tank water base on the tank heater 
selection (internal or external) 
Force Heater Control start condition: 
-  Force heater request ON by user OR auto turn ON by remote controller during error AND 
(Force Heater mode can be operate regardless of mode selection, remocon will send the lastest mode 
selection and force bit to indoor. Indoor will judge to turn ON heater to room side if it is heat mode selected, 
and turn ON heater to heat up tank water base on tank heater selection) 
-  During Error Happen (exclude the error list below) 
Error List not allow Force Heater Operation 
 
H12 
  Capacity Mismatch 
H76 
  Indoor-Remote Controller Communication Error 
H20 
  Abnormal Water Pump 
H95 
  Abnormal Voltage Connection 
H62 
  Abnormal Water Flow 
F37 
  Abnormal Water Inlet sensor 
H70 
  Abnormal Back-up Heater OLP 
F45 
  Abnormal Water Outlet sensor 
H74 
  PCB Communication Error 
 
  [ When tank mode operate with external heater selected & tank heater select ON] 
H72 
  Abnormal tank sensor 
H91 
  Abnormal tank heater OLP 
 
Force Heater Control Stop Condition: 
-  Force Heater request OFF OR 
-  Operation OFF request OR 
- Power 
reset 
OR 
-  Error of above list happens during force heater operation. 
 
Control contents: 
1)  After fulfil start condition, indoor will operate the force heater operation according to below mode condition 
 
Heat mode Only 
:  Turn ON backup heater to achieve room heat pump target water temperature. 
 
Heat + Tank mode 
:  Turn ON backup heater to heat up room OR Turn ON Heater to Boil up tank water. 
 
Cool mode Only  
:  Water pump and backup heater will OFF in force heater mode 
 
Cool + Tank mode 
:  Operate pump and internal Heater OR External heater to Boil up tank water. 
 
Tank mode Only 
:  Operate pump and internal Heater OR External heater to Boil up tank water. 
 
* For heat mode condition, backup heater will only turn ON if the backup heater is enable regardless of Room 
 
  Heater Selection 
 
* For tank mode condition, If internal heater selected backup heater will turn ON to boil up tank water. 
 
If external heater selected, booster heater will turn ON to boil up tank water regardless of tank heater 
 selection 
 
Room Side: (Heat Mode) 
1)  When force heater mode start condition fulfilled, turn ON water pump and turn ON backup heater follow 
below control. 
2)  Operate the 3 ways valve at room side only and turn ON 2 ways valve as heat mode operation. 
3)  Turn ON the zone pump and mixing valve if system select 2 zone system or Buffer tank connect YES, control 
according to normal zone pump and mixing valve control. 
4)  When Force heater mode stop condition fulfilled, turn OFF heater as below condition and turn OFF water 
pump after pump delay time. 
 
Backup Heater On Condition: 
a)  When Force Heater Control start condition fulfill AND 
b)  After water pump operate 2 minute AND 
c)  When water outlet temperature < water set temperature + [-4°C] AND 
d)  20 minutes since previous Backup heater Off AND 
e)  Backup Heater Enable 
 
Backup Heater Stop condition 
a)  Force mode off OR 
b) Operation 
off 
OR 
c)  When water outlet temperature > water set temperature + [-2°C] for continuous 15 secs OR 
* ON/OFF follow normal heater sequence. 