12.15 Alternative Outdoor Ambient Sensor Control 
Purpose of the Alternative Outdoor Ambient Sensor: 
-  It is some possibility that the air to water heat pump unit will install at a location where the original ambient 
sensor is expose to direct sunlight. Therefore, another optional ambient sensor can be connect to indoor 
PCB and locate at new and better reading location to improve the heat pump performance. 
 
Control Detail: 
-  Remocon can select either the extra outdoor ambient sensor is connected or not. (YES/NO) 
-  The alternative outdoor ambient sensor will connect to indoor unit main PCB terminal. 
 
a)  when alternative sensor select NO 
-  Original Outdoor temperature sensor will use for Indoor & Outdoor heat pump operation reference sensor. 
-  Data communication direction : OUTDOOR send outdoor temperature reading to INDOOR. 
-  Error judge : OUTDOOR will judge the original outdoor sensor error (F36 display if error detect). No 
judge error on alternative outdoor sensor 
 
b)  when alternative sensor select YES 
-  Alternative Outdoor temperature sensor will use for Indoor & Outdoor heat pump operation reference 
sensor. 
-  Data communication direction : INDOOR send outdoor temperature reading to OUTDOOR. 
-  Error judge : INDOOR will judge the Extra outdoor sensor error only after operation ON request received 
from remocon. 
(F36 display if error detect). No judge error on original outdoor sensor. 
12.16  Force DHW mode 
Purpose: 
When user want to use hot water now, user can press this force DWH mode under the quick menu to operate tank 
only mode to boil up the tank temperature. 
 
Remocon setting: 
Force DHW function can be activate under quick menu. 
 
Control Content: 
a)  when press the Force DHW function during operation OFF condition: 
-  When receive this Force DHW bit from remocon, indoor will run tank only mode regardless of the mode 
selection. 
-  After tank temperature achieve tank thermo off temperature, turn OFF force DHW bit and return to operation 
OFF with previous mode selection. 
 
b)  When press the Force DHW function during operation ON condition: 
-  When receive this Force DHW bit from remocon, indoor will memories the running mode and run tank only 
mode regardless of the mode selection. 
-  After tank temperature achieve tank thermo off temperature, turn OFF force DHW bit and return to previous 
memories running mode. 
 
* when operation OFF or mode change request from remocon during force DHW mode operation, End force 
DHW mode and follow the new request operation. 
 
* Once receive force DHW mode from remocon, indoor direct start tank mode and consider tank thermo ON. 
Thermo OFF only when achieve tank thermo OFF depend on the Tank System Setting. 
 