12.7.3  Internal Heater Control at Tank Mode 
  Internal heater turn ON condition: 
1)  Internal Heater select for Tank heater by remote controller 
2)  Tank Heater select ON by user. 
3)  Backup Heater Enable 
4)  Tank Temperature < Tank Set Temperature 
5)  Heat Pump Thermo OFF 
6)  20 minutes from previous heater off. 
 
  Room heater turn OFF condition: 
1)  Tank Temperature > Tank Set Temperature + [0°C] for continuous 15 seconds. OR 
2)  Heat Pump Thermo ON OR 
3)  Mode Change or Operation OFF by remote controller OR 
 
* Backup Heater Turn ON/OFF all together according to the selected heater capacity. 
 
65°C
Time
Tank Temp.
Tank Water Set Temp.
Backup
Heater
Operation
Heat Pump
Operation
 