WH-MXC16G9E8 - Panasonic Air Conditioner Service Manual (repair manual). Page 105

Read Panasonic WH-MXC16G9E8 Service Manual online

105 
16.5.13  Indoor/Outdoor Abnormal Communication (H90) 
 
Malfunction Decision Conditions: 
During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is 
checked whether it is normal. 
 
Malfunction Caused: 
1.  Faulty outdoor unit PCB (main). 
2.  Faulty indoor unit PCB (main). 
3.  Indoor-outdoor signal transmission error due to wrong wiring. 
4.  Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor 
and outdoor units. 
5.  Indoor-outdoor signal transmission error due to disturbed power supply waveform. 
 
Abnormality Judgment: 
Continue for 1 minute after operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 