16.5.17  Indoor Freeze-up Protection (H99) 
 
Malfunction Decision Conditions: 
During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. 
 
Malfunction Caused: 
1.  Faulty water pump. 
2.  Insufficient water flow rate in system. 
3.  Water leak in system. 
4.  2 way valve partially closed. 
5.  Clogged expansion valve or strainer. 
6.  Refrigerant shortage (refrigerant leakage). 
7.  Faulty indoor refrigerant liquid temperature sensor. 
8.  Faulty indoor unit PCB (main). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 