16.5.16  Outdoor High Pressure Protection (H98) 
 
Malfunction Decision Conditions: 
During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. 
 
Malfunction Caused: 
1.  Faulty water pump. 
2.  Insufficient water flow rate in system. 
3.  Water leak in system. 
4.  2/3 way closed. 
5.  Clogged expansion valve or strainer. 
6.  Excessive refrigerant. 
7.  Faulty outdoor high pressure sensor. 
8.  Faulty outdoor unit PCB (main). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 