  Multi Split Combination Possibility: 
o
  A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE. 
o
  A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE. 
o
  A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE. 
o
  A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E27PBE. 
o
  A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE. 
 
CONNECTABLE 
INDOOR UNIT 
OUTDOOR UNIT 
CU-2E15PBE
CU-2E18PBE
CU-3E18PBE CU-4E23PBE 
Type/ROOM 
A B A B A B C A B 
Wall
 
1.6kW CS-ME5PKE 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.0kW 
CS-E7PKEW 
CS-XE7PKEW 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
2.5kW 
CS-E9PKEW 
CS-XE9PKEW 
CS-ME9PD3EA 
CS-ME9PB4EA 
CS-E9GFEW 
CS-E9GFEW-2 
CS-E9PD3EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
3.2kW 
CS-E12PKEW 
CS-XE12PKEW 
CS-ME12PD3EA 
CS-ME12PB4EA 
CS-E12GFEW 
CS-E12GFEW-2 
CS-E12PD3EA 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
● 
4.0kW 
CS-E15PKEW 
CS-XE15PKEW 
– – – – ● 
● 
● 
● 
● 
● 
● 
5.0kW 
CS-E18PKEW 
CS-XE18PKEW 
CS-ME18PD3EA 
CS-ME18PB4EA 
CS-E18GFEW 
CS-E18GFEW-2 
– – – – ● 
● 
● 
● 
● 
● 
● 
6.0kW 
CS-E21PKEW 
CS-XE21PKEW 
CS-ME21PB4EA 
– – – – – – – ● 
● 
● 
● 
Capacity range of connectable 
indoor units 
From 3.2kW
to 5.6kW 
From 3.2kW
to 6.4kW 
From 4.5kW 
to 9.0kW 
From 4.5kW 
to 11.0 kW 
Pipe length 
1 room maximum  
pipe length (m) 
20 20  25 
25 
Allowable elevation (m) 
10 
10 
15 
15 
Total allowable pipe 
length (m) 
30 30  50 
60 
Total pipe length for 
maximum chargeless 
length (m) 
20 20  30 
30 
Additional gas 
amount over 
chargeless length (g/m) 
15 15  20 
20 
Note: “●” : Available
Remarks for CU-2E15PBE / CU-2E18PBE 
1. At least two indoor units must be connected. 
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within 
    connectable capacity range of indoor unit. (as shown in the table above) 
    Example: The indoor units’ combination below is possible to connect to CU-2E15PBE. 
    (Total nominal capacity of indoor units is between 3.2kW to 5.6kW) 
    1) Two CS-E7PKEW only (Total nominal cooling capacity is 4.0kW) 
    2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW) 
Remarks for CU-3E18PBE / CU-4E23PBE 
1. At least two indoor units must be connected. 
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within 
    connectable capacity range of indoor unit. (as shown in the table above) 
    Example: The indoor units’ combination below is possible to connect to CU-3E18PBE. 
    (Total nominal capacity of indoor units is between 4.5kW to 9.0kW) 
    1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW) 
     2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW) 
 
 
 
 
 