AE-XM24CR (serv.man11). Troubleshooting of control circuit - Sharp Air Conditioner Service Manual (repair manual). Page 4

Read Sharp AE-XM24CR (serv.man11) Service Manual online

50
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
3  When all rooms are not heated
Does the air get cooler in the 
cooling operation mode?
Check the four-way valve. 
Has the cycle been switched? 
Replace the outdoor 
relay PWB. 
Is AC230V applied between 
the connector(CN4) 1 and 3 
of the 4-way valve ?
Replace the four-way valve.
Pressure check
The heating cycle is normal. 
Refer to (1) All rooms are 
not cooled.
Press the ON switch on the
 remote control to run the air 
conditioner. 
Set the temperature to 32˚C 
in the heating mode and 
start operation. 
Is the outdoor compressor
 running?
Yes
Yes
Yes
Yes
No
No
No
Page of 4