AE-XM24CR (serv.man11). Troubleshooting of control circuit - Sharp Air Conditioner Service Manual (repair manual). Page 3

Read Sharp AE-XM24CR (serv.man11) Service Manual online

49
AY-XM7/9/12CR
AY-XPM7/9/12CR
AE-XM18/24CR
2
Yes
Yes
No
Yes
No
No
No
Yes
No
No
Yes
Yes
Short circuit of the thermistor error
Open circuit of the thermistor error
Is the resistance value of the 
thermistor for UNIT A (TH5), 
UNIT B (TH6) or UNIT C (TH7) 
Open circuit of serial signal line
Short circuit of serial signal line
When one room is not cooled (other rooms are cooled)
Is the timer lamp of the 
indoor unit in the room 
not cooled flashing ?
Press the OPERATION 
button to start operating 
the air-conditioner.
(Set the cooling mode 
to 18˚C.)
Is the timer lamp of the 
indoor unit in the room 
not cooled flashing ?
Check that the power 
between the terminal 
board "N" and "1" of the 
indoor unit is AC 230V.
Repair the wiring 
between the units.
Replace the indoor 
control PWB.
Replace the thermistor.
Check the failure 
symptom with the failure 
diagnosis mode.
Replace the outdoor control 
PWB 
or the exppansion valve (UNIT A)
or the exppansion valve (UNIT B)
or the exppansion valve (UNIT C)
Is the resistance value of the 
winding in the fan motor 
?
(Between 1 and 3 of CN1)
Abnormal fan motor of  
indoor unit
The thermal fuse is blown.
The motor is locked.
Replace the indoor fan motor.
Is the wiring between the 
units connected by mistake 
or broken ?
Repair the wiring between 
the units.
Replace the indoor control PWB.