AE-M18 (serv.man2) - Sharp Air Conditioner Service Manual (repair manual). Page 23

Read Sharp AE-M18 (serv.man2) Service Manual online

23
AY-M09AE
AE-M18AE
The room is not cooled at all
or not cooled.
The compressor does not operate.
Measure resistances of TH1 and TH2.
Push the "TEST" and  "AUX" on 
the indoor unit.
The room is not heated at all or not heated.
The compressor does not operate.
Same as "The room is not cooled 
at all or not cooled.
Refer to trouble suspension table.
Is the 3A fuse down ?
Replace the fuse and varistor 
with new ones.
NO
NO
YES
Replace the transformer 
with a new one.
YES
Three LEDs are all lit.
Is the measured value 
approx. 16.0Vac ?
Replace the PWB 
with a new one.
Using a tester, measure the 
voltage between terminal"1" and 
"2" of connector CN2 on the 
P.W.B. ass'y.
Measure the secondary 
voltage of transformer.