U-50PE2E5A, U-100PE1E8A, U-100PEY1E8, U-125PE1E8A, U-125PEY1E8, U-140PE1E8A, U-140PEY1E8, S-100PU2E5B, S-125PU2E5B, S-140PU2E5B, S-71PU2E5B, S-100PF1E5B, S-125PF1E5B, S-140PF1E5B, S-71PF1E5B - Panasonic Air Conditioner Service Manual (repair manual). Page 19

Read Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual online

1-1-1-5
1
1
Simultaneous (Double-Twin) -Type
1-1.  Unit Specifications
PE1
1. 4-Way Cassette Type S-36PU2E5B×4 / U-125PE1E5A
INDOOR
MODEL
S-36PU2E5B×4
-
-
PANEL
MODEL
Standard type:CZ-KPU3 ×4 / ECONAVI type:CZ-KPU3A ×4
-
-
OUTDOOR
MODEL
-
U-125PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1 × 3
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
12.5 
12.5 
12.5 
-
-
-
3.3 
14.0 
BTU/h
42700
42700
42700
-
-
-
11300 
47800 
Current
A
0.23 ×4
0.23 ×4
0.22 ×4
15.3 
14.8 
14.3 
-
-
Input power
W
24 ×4
24 ×4
24 ×4
3.274k
3.274k
3.274k
-
-
TOTAL W
-
3.370k
3.370k
3.370k
770
4.600k
Annual consumption
TOTAL kWh *
4
-
-
-
-
1685
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.70 
3.70/A
3.70 
4.29
3.04
Erp
*
6
Pdesign
kW
-
-
-
-
12.5
-
-
-
η 
s,c
%
-
-
-
-
277.5
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
H
E
A
T
I
N
G
Capacity
kW
14.0 
14.0 
14.0 
-
-
-
4.1 
16.0 
BTU/h
47800
47800
47800
-
-
-
14000 
54600 
Current
A
0.22 ×4
0.22 ×4
0.21×4
13.8 
13.4 
12.9 
-
-
Input power
W
22 ×4
22 ×4
22 ×4
2.952k
2.952k
2.952k
-
-
TOTAL W
-
3.040k
3.040k
3.040k
790
5.040k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.60 
4.60/A
4.60 
5.19
3.17
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
12.5
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
η 
s,h
%
-
-
-
-
161.0
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
-
-
Class
-
-
-
-
-
-
-
-
Power factor
%
-
-
-
97 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
53/-
-
-
Power Level dB
-
70/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.23×4/24×4 0.23×4/24×4 0.22×4/24×4 28.0 / 6.00k 28.0 / 6.20k 28.0 / 6.40k
-
Starting current(A) / Comp output(W)
-
-
-
15.3 / 3.0k
14.8 / 3.0k
14.3 / 3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
90 × 2
-
Moisture removal volume
L/h(Pt/h)
2.8
(0.7×4)
(5.9)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
14.5×4/13.0×4/11.5×4 (512)×4/(459)×4/(406)×4
-
-
-
Heating
m³/min (ft³/min)
14.5×4/13.0×4/11.5×4 (512)×4/(459)×4/(406)×4
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
130.0 (4591)
-
-
Heating
m³/min (ft³/min)
-
110.0 (3885)
-
-
Refrigerant type / amount g(oz)
-
R410A  
3.40k
(119.9)
-
Product dimension
Height mm(inch)
256 
(10-5/64)
1416 (55-3/4)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
1556 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
19 
(42)
98
(216)
-
(GROSS)  kg(lb)
26 
(57)
108
(238)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 75m (16.4 ~246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  
η 
s,c
 and 
η 
s,h
 classification is at 230V(400V) only in accordance with EN-14825. For heating, 
η 
s,h
 indicates the value of only Average heating season.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   5
19/09/26   17:01:06
Page of 127
Display