U-50PE2E5A, U-100PE1E8A, U-100PEY1E8, U-125PE1E8A, U-125PEY1E8, U-140PE1E8A, U-140PEY1E8, S-100PU2E5B, S-125PU2E5B, S-140PU2E5B, S-71PU2E5B, S-100PF1E5B, S-125PF1E5B, S-140PF1E5B, S-71PF1E5B - Panasonic Air Conditioner Service Manual (repair manual). Page 17

Read Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual online

1-1-1-3
1
1
Simultaneous (Twin) -Type
1-1.  Unit Specifications
1. 4-Way Cassette Type S-36PU2E5B×2 / U-71PE1E5A
PE1
INDOOR
MODEL
S-36PU2E5B×2
-
-
PANEL
MODEL
Standard type:CZ-KPU3 ×2 / ECONAVI type:CZ-KPU3A ×2
-
-
OUTDOOR
MODEL
-
U-71PE1E5A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO5151  /  EN14511  /  EN12102  /  EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
7.1 
7.1 
7.1 
-
-
-
2.5 
8.0 
BTU/h
24200
24200
24200
-
-
-
8500 
27300 
Current
A
0.23 ×2
0.23 ×2
0.22 ×2
8.40 
8.15 
7.90 
-
-
Input power
W
24 ×2
24 ×2
24 ×2
1.762k
1.762k
1.762k
-
-
TOTAL W
-
1.810k
1.810k
1.810k
450
2.650k
Annual consumption
TOTAL kWh *
4
-
-
-
-
905
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
3.92 
3.92/A
3.92 
5.56
3.02
Erp
*
6
Pdesign
kW
-
-
-
-
7.1 
-
-
-
SEER
(W/W)
-
-
-
-
7.4 
-
-
-
Annual consumption
kWh
-
-
-
-
336
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
95 
94 
93 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
48/-
-
-
Power Level dB
-
65/-
-
-
H
E
A
T
I
N
G
Capacity
kW
8.0 
8.0 
8.0 
-
-
-
2.0 
9.0 
BTU/h
27300
27300
27300
-
-
-
6800 
30700 
Current
A
0.22 ×2
0.22 ×2
0.21 ×2
8.65 
8.25 
8.00 
-
-
Input power
W
22 ×2
22 ×2
22 ×2
1.826k
1.826k
1.826k
-
-
TOTAL W
-
1.870k
1.870k
1.870k
400
2.850k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.28 
4.28/A
4.28 
5.00
3.16
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
7.1 
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.3 
-
-
-
Annual consumption
kWh
-
-
-
-
2312
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
96 
96 
95 
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
50/-
-
-
Power Level dB
-
67/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.23×2/24×2 0.23×2/24×2 0.22×2/24×2 18.0 / 3.80k 18.0 / 3.93k 18.0 / 4.06k
-
Starting current(A) / Comp output(W)
-
-
-
8.65 / 2.0k
8.25 / 2.0k
8.00 / 2.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
90 
-
Moisture removal volume
L/h(Pt/h)
1.4
(0.7×2)
(2.9)
-
-
External static pressure
Pa
-
-
-
Indoor  
Air flow *
7
Cooling
m³/min (ft³/min)
14.5×2/13.0×2/11.5×2 (512)×2/(459)×2/(406)×2
-
-
-
Heating
m³/min (ft³/min)
14.5×2/13.0×2/11.5×2 (512)×2/(459)×2/(406)×2
-
-
-
Outdoor  
Air flow
Cooling
m³/min (ft³/min)
-
60.0 (2119)
-
-
Heating
m³/min (ft³/min)
-
60.0 (2119)
-
-
Refrigerant type / amount g(oz)
-
R410A  
2.35k
(82.9)
-
Product dimension
Height mm(inch)
256 
(10-5/64)
996 (39-7/32)
-
Width
mm(inch)
840 
(33-5/64)
940 (37-1/32)
-
Depth
mm(inch)
840 
(33-5/64)
340 (13-13/32)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
Packing dimension
Height mm(inch)
302 
(11-57/64)
1136 
-
Width
mm(inch)
898 
(35-3/8)
1055 
-
Depth
mm(inch)
898 
(35-3/8)
485 
-
Weight
(NET)
kg(lb)
19 
(42)
69
(152)
-
(GROSS)  kg(lb)
26 
(57)
77
(170)
-
Panel (NET)  kg(lb)
(11)
-
-
Layers limit (actually)
11 (12)
2 (3)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range     m (ft)
5 ~ 50m (16.4 ~164)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m (0.538)
-
Pipe length for additional gas  m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6  SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data  
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb   3
19/09/26   17:01:05
Page of 127
Display

Click on the first or last page to see other U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B service manuals if exist.