Read Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual online
1-1-1-2
1
1
Single -Type
1-1. Unit Specifications
1. 4-Way Cassette Type S-36PU2E5B / U-36PE2E5A
PE2
INDOOR
MODEL
S-36PU2E5B
-
-
PANEL
MODEL
Standard type:CZ-KPU3 / ECONAVI type:CZ-KPU3A
-
-
OUTDOOR
MODEL
-
U-36PE2E5A
-
Branch pipe
MODEL
-
Performance test condition
ISO5151 / EN14511 / EN12102/ EN14825
Power supply
Ø, Hz
1Ø 50Hz
1Ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
Capacity
kW
3.6
3.6
3.6
-
-
-
1.5
4.0
BTU/h
12300
12300
12300
-
-
-
5100
13600
Current
A
0.23
0.23
0.22
3.75
3.55
3.40
-
-
Input power
W
24
24
24
0.746k
0.746k
0.746k
-
-
TOTAL W
-
0.770k
0.770k
0.770k
240
910
Annual consumption
TOTAL kWh *
4
-
-
-
-
385
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.68
4.68/A
4.68
6.25
4.40
Erp
*
6
Pdesign
kW
-
-
-
-
3.6
-
-
-
SEER
(W/W)
-
-
-
-
7.4
-
-
-
Annual consumption
kWh
-
-
-
-
170
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
91
91
91
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
45/-
-
-
Power Level dB
-
64/-
-
-
H
E
A
T
I
N
G
Capacity
kW
4.0
4.0
4.0
-
-
-
1.5
5.0
BTU/h
13600
13600
13600
-
-
-
5100
17100
Current
A
0.22
0.22
0.21
3.80
3.60
3.45
-
-
Input power
W
22
22
22
0.758k
0.758k
0.758k
-
-
TOTAL W
-
0.780k
0.780k
0.780k
190
1.080k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
5.13
5.13/A
5.13
7.89
4.63
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
3.6
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
4.6
-
-
-
Annual consumption
kWh
-
-
-
-
1095
-
-
-
Class
-
-
-
-
A++
-
-
-
Power factor
%
-
-
-
91
91
91
-
-
Noise indoor
dB-A (H/M/L) *
7
30/28/27
-
-
-
Power Level dB
45/43/42
-
-
-
Noise outdoor
dB-A (H/L)
-
46/-
-
-
Power Level dB
-
66/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
0.23/24
0.23/24
0.22/24
11.0 / 2.20k
11.0 / 2.30k
11.0 / 2.40k
-
Starting current(A) / Comp output(W)
-
-
-
3.80 / 1.1k
3.60 / 1.1k
3.45 / 1.1k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
60
60
-
Moisture removal volume
L/h(Pt/h)
0.7
(1.5)
-
-
External static pressure
Pa
-
-
-
Indoor
Air flow *
7
Cooling
m³/min (ft³/min)
14.5/13.0/11.5 (512)/(459)/(406)
-
-
-
Heating
m³/min (ft³/min)
14.5/13.0/11.5 (512)/(459)/(406)
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
38.0 (1342)
-
-
Heating
m³/min (ft³/min)
-
38.0 (1342)
-
-
Refrigerant type / amount g(oz)
-
R410A
1.40k
(49.4)
-
Product dimension
Height mm(inch)
256
(10-5/64)
619
(24-3/8)
-
Width
mm(inch)
840
(33-5/64)
799
(31-29/64)
-
Depth
mm(inch)
840
(33-5/64)
299
(11-49/64)
-
Product dimension (Panel) H×W×D mm, inch
33.5×950×950
1-11/32 × 37-13/32 × 37-13/32
-
-
Packing dimension
Height mm(inch)
302
(11-57/64)
688
-
Width
mm(inch)
898
(35-3/8)
931
-
Depth
mm(inch)
898
(35-3/8)
422
-
Weight
(NET)
kg(lb)
19
(42)
39
(86)
-
(GROSS) kg(lb)
26
(57)
44
(97)
-
Panel (NET) kg(lb)
5
(11)
-
-
Layers limit (actually)
11 (12)
5 (6)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
3 ~ 40m (9.8 ~131.2)
-
Indoor unit & Outdoor unit height difference m (ft)
15m(OD located lower)/30m(OD located higher) (49.2/98.4)
-
Add gas amount g/m (oz/ft)
20g/m (0.215)
-
Pipe length for additional gas m (ft)
30m (98.4)
-
*1 In case it is necessary to indicate the air flow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other fiche data
indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1)
SM830274-02_欧州向けR410Aシングル_TD&SM.indb 2
19/09/26 17:01:05