CW-C71YE, CW-C91YE - Panasonic Air Conditioner Service Manual (repair manual). Page 5

Read Panasonic CW-C71YE / CW-C91YE Service Manual online

Trouble
Check
Result
Cause
Remedy
Fan Motor won’t run
(Compressor run).
     • 
• 
• 
• 
Objects around
Fan.
     • 
• 
• 
• 
RESISTANCE
between Wires.
     • 
• 
• 
• 
Capacitor Fan
Motor.
     • 
• 
• 
• 
Main Control
Switch.
     • 
• 
• 
• 
Locked Fan.
     • 
• 
• 
• 
Shorted / Open
circuit.
     • 
• 
• 
• 
OHM Meter doesn’t
Deflect.
     • 
• 
• 
• 
No contacts at
Position Shown.
     • 
• 
• 
• 
Fan Hitting Cowling or
     • 
• 
• 
• 
Foreign Materials.
     • 
• 
• 
• 
Frozen Bearings.
     • 
• 
• 
• 
Shorted or Burned out.
     • 
• 
• 
• 
Capacitor Defect.
     • 
• 
• 
• 
Main Control Switch defect.
     • 
• 
• 
• 
Adjust Fan position setting
screw.
     • 
• 
• 
• 
Remove Foreign Materials.
     • 
• 
• 
• 
Replace Fan Motor.
     • 
• 
• 
• 
Replace Fan Motor.
     • 
• 
• 
• 
Replace Capacitor Fan.
     • 
• 
• 
• 
Replace Main Control
Switch.
Compressor won’t run (Fan
run).
     • 
• 
• 
• 
Thermostat setting.
     • 
• 
• 
• 
RESISTANCE
between Terminal
and the
Compressor Body.
     • 
• 
• 
• 
RESISTANCE
between Terminals.
     • 
• 
• 
• 
Overload Protector.
     • 
• 
• 
• 
Capacitor
Compressor.
     • 
• 
• 
• 
Thermostat.
     • 
• 
• 
• 
Main Control
Switch.
     • 
• 
• 
• 
Higher than room
temp.
     • 
• 
• 
• 
Shorted.
     • 
• 
• 
• 
Shorted.
     • 
• 
• 
• 
Infinity between
Terminals.
     • 
• 
• 
• 
OHM Meter doesn’t
deflect.
     • 
• 
• 
• 
No click heard.
     • 
• 
• 
• 
No contacts at
Position Shown.
     • 
• 
• 
• 
Winding Coil touched to
the compressor shell.
     • 
• 
• 
• 
Rear Shorted or Burnt out.
     • 
• 
• 
• 
Overload Protector defect.
     • 
• 
• 
• 
Capacitor defect.
     • 
• 
• 
• 
Thermostat defect.
     • 
• 
• 
• 
Main Control Switch defect.
     • 
• 
• 
• 
Set it lower.
     • 
• 
• 
• 
Replace Compressor.
     • 
• 
• 
• 
Replace Compressor.
     • 
• 
• 
• 
Replace Overload
Protector.
     • 
• 
• 
• 
Replace Capacitor
Compressor.
     • 
• 
• 
• 
Replace Thermostat.
     • 
• 
• 
• 
Replace Main Control
Switch.
Air Swing won’t run.
     • 
• 
• 
• 
Main Control
Switch.
     • 
• 
• 
• 
Air Swing Switch.
     • 
• 
• 
• 
Resistance
between wires.
     • 
• 
• 
• 
High or Low Fan
setting.
     • 
• 
• 
• 
OFF position.
     • 
• 
• 
• 
No contact at
position.
     • 
• 
• 
• 
OHM Meter doesn’t
deflect.
     • 
• 
• 
• 
Open circuit.
     • 
• 
• 
• 
Shorted or open circuit.
     • 
• 
• 
• 
Set it High or Low Cool.
     • 
• 
• 
• 
Set it ON.
     • 
• 
• 
• 
Replace Air Swing Switch.
     • 
• 
• 
• 
Replace Air Swing Motor.
Insufficient cooling.
     • 
• 
• 
• 
Thermostat Setting.
     • 
• 
• 
• 
Ventilation door
open.
     • 
• 
• 
• 
Air filter dirty.
     • 
• 
• 
• 
Location of
installation.
     • 
• 
• 
• 
Evaporator /
Condenser Coil
obstructed.
     • 
• 
• 
• 
Unit capacity for
the room too small.
     • 
• 
• 
• 
Temp difference
and running
current.
     • 
• 
• 
• 
Higher than room
temp.
     • 
• 
• 
• 
Open.
     • 
• 
• 
• 
Clogged or dirty.
     • 
• 
• 
• 
Sunlight hitting
outdoor side.
     • 
• 
• 
• 
Obstacles.
     • 
• 
• 
• 
Clogged or dirty.
     • 
• 
• 
• 
Not satisfied.
     • 
• 
• 
• 
REFER TO
PERFORMANCE
EVALUATION.
     • 
• 
• 
• 
Reduces capacity.
     • 
• 
• 
• 
Restricted air circulation.
     • 
• 
• 
• 
Restricted Heat Exchanger.
     • 
• 
• 
• 
Restricted Heat Exchanger.
     • 
• 
• 
• 
Restricted air circulation.
     • 
• 
• 
• 
Leakage of refrigerant or
refrigeration system is
blocked.
     • 
• 
• 
• 
Set it lower.
     • 
• 
• 
• 
Close Vent. door.
     • 
• 
• 
• 
Clean or replace Air Filter.
     • 
• 
• 
• 
Consider building an
AWNING.
     • 
• 
• 
• 
Remove obstacles or
reinstall unit.
     • 
• 
• 
• 
Clean the coils.
     • 
• 
• 
• 
Replace the unit with
bigger one.
     • 
• 
• 
• 
Locate repair leak.
     • 
• 
• 
• 
Flush refrigeration cycle.
Noise.
     • 
• 
• 
• 
Source of Noise
     • 
• 
• 
• 
Vibration.
     • 
• 
• 
• 
Intermittent Noise.
     • 
• 
• 
• 
Faulty installation.
     • 
• 
• 
• 
Fan hitting objects.
     • 
• 
• 
• 
Refrigerant tubing touching
each other.
     • 
• 
• 
• 
Fan splashing Drain Water.
     • 
• 
• 
• 
Reinstall unit or Reinforce
the installation.
     • 
• 
• 
• 
Adjust Fan position or
remove foreign materials.
     • 
• 
• 
• 
About 1/2” Clearance
needed.
     • 
• 
• 
• 
Normal occurrence.
Water dripping inside room.
     • 
• 
• 
• 
Unit installation.
     • 
• 
• 
• 
Drain Tray-
Styrofoam pieces
blocking drain
channel.
     • 
• 
• 
• 
Tilted to inside room.
     • 
• 
• 
• 
Clogged.
     • 
• 
• 
• 
Restricted run off.
     • 
• 
• 
• 
Clogged or blocked.
     • 
• 
• 
• 
Tilt unit to outside slightly.
     • 
• 
• 
• 
Remove the foreign
materials.
Frozen Evaporator
     • 
• 
• 
• 
Thermostat setting.
     • 
• 
• 
• 
Air filter /
Evaporator.
     • 
• 
• 
• 
Temp. difference
and running
current.
     • 
• 
• 
• 
Set too low for
ambient conditions.
     • 
• 
• 
• 
Clogged or Dirty.
     • 
• 
• 
• 
REFER TO
PERFORMANCE
EVALUATION.
     • 
• 
• 
• 
Outdoor temp. low (Night
time).
     • 
• 
• 
• 
Restricted air circulation.
     • 
• 
• 
• 
Leakage of refrigerant or
refrigeration system is
blocked.
     • 
• 
• 
• 
Set the Main Control Knob
to Fan to melt ice and set
the Temp. Control to
higher temperature.
     • 
• 
• 
• 
Clean Air filter /
Evaporator.
     • 
• 
• 
• 
Locate and repair leak.
     • 
• 
• 
• 
Flush refrigeration cycle.
5