Read Panasonic CW-C71YE / CW-C91YE Service Manual online
4.2. CW-C71YE
Item
Pressure (MPa)
Temperature (°C)
A
1.86 ~ 2.06
70 ~ 85
B
1.81 ~ 2.01
31 ~ 41
C
0.59 ~ 0.66
8 ~ 14
D
0.54 ~ 0.59
13 ~ 21
Note: Indoor temperature at 27°C (DB), 19°C (WB) and Outdoor at
35°C (DB), 24°C (WB).
35°C (DB), 24°C (WB).
4.3. CW-C91YE
Item
Pressure (MPa)
Temperature (°C)
A
1.96 ~ 2.22
71 ~ 89
B
1.91 ~ 2.06
35 ~ 45
C
0.56 ~ 0.63
7 ~ 12
D
0.50 ~ 0.56
6 ~ 14
Note: Indoor temperature at 27°C (DB), 19°C (WB) and Outdoor at
35°C (DB), 24°C (WB).
35°C (DB), 24°C (WB).
4 Refrigeration Cycle Diagram
4.1.
5 Air Conditioner Performance Evaluation
Intake & Discharge Air
Temperature Difference
Current Drain
Determination
Remedy
•
•
•
•
8°C and over (14.4°F)
•
•
•
•
As specified.
•
•
•
•
Nothing wrong.
•
•
•
•
None.
•
•
•
•
8°C and over (14.4°F)
•
•
•
•
Higher than specified.
•
•
•
•
Nothing wrong, outdoor
temperature is too high, heat
radiation is not efficient.
temperature is too high, heat
radiation is not efficient.
•
•
•
•
Improve heat radiation.
•
•
•
•
Under 8°C (14.4°F)
•
•
•
•
Higher than specified.
•
•
•
•
Something is preventing heat
radiation.
radiation.
•
•
•
•
Excessive amount of refrigerant.
•
•
•
•
Improve heat radiation.
•
•
•
•
Under 8°C (14.4°F)
•
•
•
•
Lower than specified.
•
•
•
•
Leakage of refrigerant or
refrigerant system is blocked.
refrigerant system is blocked.
•
•
•
•
Locate repair leak.
•
•
•
•
Flush refrigeration cycle.
•
•
•
•
Under 8°C (14.4°F)
•
•
•
•
Higher than specified by
50%.
50%.
•
•
•
•
Compressor defect.
•
•
•
•
Replace the compressor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
6 Troubleshooting Guide
Warning: Disconnect unit from electrical power supply before making any electrical checks.
Trouble
Check
Result
Cause
Remedy
Fan Motor and Compressor
won’t run.
won’t run.
•
•
•
•
Supply Voltage
•
•
•
•
Fuse Box or Circuit
Breaker.
Breaker.
•
•
•
•
Power cord or
Wiring Harness.
Wiring Harness.
•
•
•
•
Thermostat Setting.
•
•
•
•
Less than 10% by
Rated.
Rated.
•
•
•
•
Open Contacts.
•
•
•
•
Pulled loose or
Shorted.
Shorted.
•
•
•
•
Higher than room
temp.
temp.
•
•
•
•
Temporary or Permanent?
•
•
•
•
Customer Restarted unit
immediately without waiting
3 minutes.
immediately without waiting
3 minutes.
•
•
•
•
Consult ELECTRICIAN, If
permanent.
permanent.
•
•
•
•
Repair Open Circuit.
•
•
•
•
WAIT FOR 3 MINUTES.
•
•
•
•
Repair or Replace it.
•
•
•
•
Set it LOWER.
4
CW-C71YE / CW-C91YE