9.1.1. Electrical Work.
     • 
• 
• 
• 
Always use at the rated voltage and with a specific air
conditioning circuit.
     • 
• 
• 
• 
Some installation locations may require installation of a
short-circuit breaker.
     • 
• 
• 
• 
Time delay fuse or circuit breaker rating is 16 Ampere for
CW-C180EE/CW-A180EE and 20 Ampere for CW-
C240EE.
     • 
• 
• 
• 
Nominal cross sectional area of power supply wire must be
3 core x 2.5 mm
2
or above.
     • 
• 
• 
• 
The power supply must be from an independent circuit.
     • 
• 
• 
• 
All electrical installations must be made in accordance with
local wiring and safety regulations wherever applicable.
     • 
• 
• 
• 
There must be a double pole switch with minimum of 3 mm
contact gap in the fixed installation circuit.
     • 
• 
• 
• 
Please engage an authorized dealer or specialist for the
installation work.
9.1.2. Select the Best Location.
     • 
• 
• 
• 
When installing, use the nearest power socket. Make sure
the power socket is easy to reach so you can quickly
disconnect your air conditioner in case of emergency.
     • 
• 
• 
• 
Ensure that the air conditioner is well supported, securely
fastened, easily reachable and not obstructed (see
“Dimension” below).
     • 
• 
• 
• 
Avoid locations with: salty or sulphurous air, draughts,
dampness and flammable gas.
     • 
• 
• 
• 
If you install the drainage system, be sure to channel the
condensed water to a suitable location.
     • 
• 
• 
• 
Cover, obstructions and unsteady support may cause
excessive operating noise and vibration.
     • 
• 
• 
• 
The rear end of the air conditioner is splash proof. You
need not shield or cover it.
9 How to Install
9.1. Before installing the air conditioner, please read the following:
9.2. Preparation for Installation.
     • 
• 
• 
• 
There should not be any obstacles surrounding the unit.
     • 
• 
• 
• 
Prepare an installation hole that is only slightly bigger than the cabinet size.
     • 
• 
• 
• 
Left and right side of the unit should be at least 150 mm away from the wall.