13.2  Relationship between the condition of the air conditioner and pressure 
and electric current 
 
Cooling Mode 
Condition of the  
air conditioner 
Low Pressure 
High Pressure 
Electric current during operation
Insufficient refrigerant 
(gas leakage) 
Ô 
Ô 
Ô 
Clogged capillary tube or 
strainer 
Ô 
Ô 
Ô 
Short circuit in the indoor unit 
Ô 
Ô 
Ô 
Heat radiation deficiency 
of the outdoor unit 
Ò 
Ò 
Ò 
Inefficient compression 
Ò 
Ô 
Ô 
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started. 
13.3   Diagnosis methods of a malfunction of a compressor 
Nature of fault 
Symptom 
Insufficient compressing 
of a compressor 
Electric current during operation becomes approximately 20% lower thank the normal value. 
The discharge tube of the compressor becomes abnormally hot (normally 70℃ to 90℃ ) 
The different between high pressure and low pressure becomes almost zero. 
Locked compressor 
Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter. In 
some cases, a breaker turns off. 
Then compressor has a humming sound. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 