CS-TZ60TKEW, CS-TZ71TKEW, CU-TZ60TKE, CU-TZ71TKE - Panasonic Air Conditioner Service Manual (repair manual). Page 12

Read Panasonic CS-TZ60TKEW / CS-TZ71TKEW / CU-TZ60TKE / CU-TZ71TKE Service Manual online

12 
Model 
Indoor CS-TZ71TKEW 
Outdoor CU-TZ71TKE 
Performance Test Condition 
EUROVENT 
Power Supply 
Phase, Hz 
Single, 50 
V 230 
 Min. 
Mid. 
Max. 
Cooling 
Capacity 
kW 
0.98 7.10 8.10 
BTU/h 3340 
24200 
27600 
Kcal/h 840 
6110 
6970 
Running Current 
– 
9.90 
– 
Input Power 
420 
2.24k 
2.67k 
Annual Consumption 
kWh 
– 
1120 
– 
EER 
W/W 
2.33 3.17 3.03 
BTU/hW 7.95 
10.80 
10.34 
Kcal/hW 
2.00 2.73 2.61 
ErP 
Pdesign kW 
7.1 
SEER (W/W) 
6.1 
Annual 
Consumption 
kWh 407 
Class  
A++ 
Power 
Factor 
– 98 – 
Indoor Noise (H / L / QLo) 
dB-A 
47 / 38 / 35 
Power Level dB 
63 / – / – 
Outdoor Noise (H / L) 
dB-A 
52 / – 
Power Level dB 
66 / – 
Heating
 
Capacity 
kW 
0.98 8.60 9.90 
BTU/h 3340 
29300 
33800 
Kcal/h 840 
7400 
8510 
Running 
Current 
– 10.90 – 
Input Power 
400 
2.45k 
2.85k 
COP 
W/W 
2.45 3.51 3.47 
BTU/hW 8.35 
11.96 
11.86 
Kcal/hW 
2.10 3.02 2.99 
ErP 
Pdesign kW 
5.5 
Tbivalent °C 
-10 
SCOP (W/W) 
4.0 
Annual 
Consumption 
kWh 1925 
Class  
A+ 
Power 
Factor 
– 98 – 
Indoor Noise (H / L / QLo) 
dB-A 
47 / 38 / 35 
Power Level dB 
63 / – / – 
Outdoor Noise (H / L) 
dB-A 
54 / – 
Power Level dB 
68 / – 
Low Temp. : Capacity (kW) / I.Power (W) / COP 
7.17 / 2.52k / 2.85 
Extr Low Temp. : Capacity (kW) / I.Power (W) / COP 
6.13 / 2.48k / 2.47 
Max Current (A) / Max Input Power (W) 
14.8 / 3.22k 
Starting Current (A) 
10.90 
 
 
 