18.4.24    F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) 
Malfunction Decision Conditions 
  During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by 
the outdoor unit heat exchanger thermistor. 
 
Malfunction Caused 
  Outdoor heat exchanger temperature rise due to short-circuit of hot discharge air flow. 
  Outdoor heat exchanger temperature rise due to defective of outdoor fan motor. 
  Outdoor heat exchange temperature rise due to defective outdoor heat exchanger thermistor. 
  Outdoor heat exchanger temperature rise due to defective of outdoor unit PCB. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 