18.4.21    F90 (Power Factor Correction Protection) 
Malfunction Decision Conditions 
  To maintain DC voltage level supply to power transistor. 
  To detect high DC voltage level after rectification. 
 
Malfunction Caused 
  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at 
the outdoor unit main PCB senses abnormal DC voltage level for power transistors. 
  When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level. 
  When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFF 
relay RY-C. 
 
Troubleshooting 
 
 
 
 
 
 