Unit
CS-PE9CKE
CU-PE9CKE
Air Circulation
Type
Cross-flow Fan
Propeller fan
Motor
Type
Transistor(8poles)
Induction (6 pole)
Input
W
56
Rated Output
W
30
15
Fan Speed
Low
rpm
820±60
Medium
rpm
1060±60
High
rpm
1300±60
670±60
Heat Exchanger
Description
Evaporator
Condenser
Tube Material
copper
copper
Fin Type
slot type
Corrugation type
Rows / Stage
(Plate fin configuration, forced draft)
2 × 15
1 × 24
FPI
18
19
Dimensions
mm
610 × 315 × 25.4
726 × 504 × 18.2
Refrigerant Control Device
Capillary Tube
Refrigeration Oil
(c.c)
RB68A or Freol Alpha68A
Refrigerant (R410A)
g
840
Thermostat
Electronic Control
Overload Protector
Protection Device
Capillary
Length
mm
600
Circulation
L/min
8.15
Inner dia
mm
1.3
Air Filter
P.P Honeycomb
Refrigerant Circulation Control Device
Capillary
Fan Motor Capacitor
µFV
1.2µF, 400V
    • 
• 
• 
• Specifications are subject to change without notice for further improvement