CS-E21JB4EA, CU-E21HBEA - Panasonic Air Conditioner Service Manual (repair manual). Page 71

Read Panasonic CS-E21JB4EA / CU-E21HBEA Service Manual online

71
15.5.24. F99 (Output Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an output over-current (20.2A) is detected by checking the current that flows in the
inverter DC peak sensing circuitry.
Malfunction Caused
• DC peak due to compressor failure.
• DC peak due to defective power transistor(s).
• DC peak due to defective outdoor unit PCB.
Troubleshooting
• Checking the power transistor.
• Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
• If unavoidable necessary to touch a live part, make sure the power transistor’s supply voltage is below 50V using the tester.
• For the UVW, make measurement at the Faston terminal on the board of the relay connector.
Page of 87
Display

Click on the first or last page to see other CS-E21JB4EA / CU-E21HBEA service manuals if exist.