15.5.22. F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor
tank temperature sensor.
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor
tank temperature sensor.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage).
• 2/3 way valve closed.
• Detection error due to faulty compressor tank temperature sensor.
• 2/3 way valve closed.
• Detection error due to faulty compressor tank temperature sensor.