AE-X108 - Sharp Air Conditioner Service Manual (repair manual). Page 31

Read Sharp AE-X108 Service Manual online

AH/AU-X108E
AY/AE-X108E
AH/AU-X138E
AY/AE-X138E
31
Function
NO
Description
Detection 
time
Restart 
condition
Restart 
times
Indoor Outdoor
Operation
Self diagnostic
display
  
AC 
overcurrent
Compressor
lock
Compressor 
overheating 
control
5
6
7
Lowers the operating frequency if the 
temperature of the compressor chamber 
thermistor (TH1) rises above 105
°
C.
Stops the compressor if the thermistor 
stays above 104
°
C for 4 minutes, or 1 
minute at minimum frequency or less.
Lowers the operating frequency if the 
compressor AC current exceeds 
Peak control level 
[10.1/8.0A (heating), 7.5/6.15A (cooling)] 
[AY-X138E/AY-X108E] 
Stops the compressor if the current 
exceeds peak control level at 40 Hz or less.
Stops the compressor if the compressor 
AC current exceeds 15A.
During 
compressor 
operation
Immediately 
after 
compressor 
activation.
During 
compressor 
operation
During 
compressor 
operation
Automatically restarts after 
safety time (170 seconds)
Automatically restarts after 
safety time (170 seconds) 
Automatically restarts after 
safety time (170 seconds)
No limit
No
No
No limit
Yes
No limit
 
Yes
No limit
No
No
Compressor
high
temperature 
error
8
Stops the compressor if the compressor 
chamber thermistor is above 114
°
C.
(Or when TH1 shorts)
During 
operation
Outdoor 
overheating 
control
9
Automatically restarts after 
safety time ( (170 seconds)
When 
compressor 
is activated
Outdoor 
thermistor 
short
10
Stops the compressor if an outdoor 
thermistor (excluding TH1) shorts.
(Except for the AU-X138E, AU-X108E)
Automatically restarts after 
safety time ( (170 seconds)
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes
When 
compressor 
is activated
Outdoor 
thermistor 
short
11
Stops the compressor if the circuit of an 
outdoor thermistor breaks.
(Except for the AU-X138E, AU-X108E)
Automatically restarts after 
safety time ( (170 seconds)
4 times
Yes
Yes
4 times
Yes
Yes
During 
compressor 
operation
AC 
abnormal 
current error
12
Stops the compressor if if the operating 
frequency is above 70 Hz and the 
compressor current is below 1.1 A/0.85 A.
[AE-X138E/AE-X108E]
Automatically restarts after 
safety time ( (170 seconds)
4 times
Yes
Yes
During 
operation
Serial 
signal error
Four-way 
valve error
13
14
Restarts after reception of 
serial signal.
Automatically restarts after 
safety time (170sec.) 
During 
operation
4 minutes after
compressor 
activation
Stops the compressor if the outdoor unit 
does not receive a serial signal from the 
indoor unit for 30 seconds.
When the rise and fall in the detected 
temperature of the outdoor heat 
exchanger thermistor (TH2) do not agree 
with the operating cycle.
Turns the compressor relay off if the 
indoor unit does not receive a serial 
signal from the outdoor unit for 8 minutes.
Stops the compressor if the compressor 
AC current exceeds 3.37/2.83A
[AY-X138E/AY-X108E] 
immediately after activating the compressor 
(at 17 to 30 Hz).
Lowers the operating frequency if the 
temperature of the outdoor heat exchanger 
rises above 57
°
C during cooling. Stops the 
compressor if the temperature stays above 
57
°
C for 4 minutes, or 1 minute at 
minimum frequency or less.
Automatically restarts less 
than 8 minutes after operation 
stops.
Automatically restarts 
when thermistor (TH1) 
temperature falls below 
100
°
C (approximately 30 
minutes)
Page of 56
Display

Click on the first or last page to see other AE-X108 service manuals if exist.