14
Item
Unit
Outdoor Unit
Power Source (Phase, Voltage, Cycle)
ø
Three
V
400
Hz
50
Input Power
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
kW
Cooling: 4.36
Heating: 3.07
Heating: 3.69
Maximum Input Power For Heatpump System
kW
6.25
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
3Ø / 9.4 / 6.25k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
3Ø / 13.0 / 9.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W)
— / — / —
Starting Current
A
6.5
Running Current
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
A
Cooling: 6.5
Heating: 4.7
Heating: 5.6
Maximum Current For Heatpump System
A
9.4
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
Power factor means total figure of compressor and
outdoor fan motor.
%
Cooling: 97
Heating: 95
Heating: 95
Power Cord
Number of core
—
Length
m (ft)
—
Thermostat
Electronic Control
Protection Device
Electronic Control
Item
Unit
Indoor Unit
Performance Test Condition
EN 14511
Operation Range
Outdoor Ambient
°C
Cooling: 16 ~ 43
Heating: -20 ~ 35
Water Outlet
°C
Cooling: 5 ~ 20
Heating: 25 ~ 55
Internal Pressure Differential
kPa
Cooling: 31.5
Heating: 45.0
Heating: 45.0
Noise Level
Condition
(Ambient/Water)
A35W7
A7W35
A2W35
dB (A)
Cooling: 33
Cooling: 33
—
Power Level dB
Cooling: 46
Cooling: 46
—
Dimension
Height
mm (inch)
892 (35-1/8)
Width
mm (inch)
502 (19-3/4)
Depth
mm (inch)
353 (13-29/32)
Net Weight
kg (lbs)
47 (104)
Refrigerant Pipe Diameter
Liquid
mm (inch)
9.52 (3/8)
Gas
mm (inch)
15.88 (5/8)
Water Pipe Diameter
Inlet
mm (inch)
28 (1-3/32)
Outlet
mm (inch)
28 (1-3/32)
Water Drain Hose Inner Diameter
mm (inch)
15 (19/32)
Pump
Motor Type
DC Motor
No. of Speed
7 (Software Selection)
Input Power
W
76
Hot Water Coil
Type
Brazed Plate
No. of Plates
44
Size (W × H × L)
mm
80 × 120 × 376
Water Flow Rate
l/min (m
3
/h)
Cooling: 33.0 (2.0)
Heating: 40.1 (2.4)
Heating: 40.1 (2.4)
Pressure Relief Valve Water Circuit
kPa
Open: 300, Close: 265 and below
Flow Switch
Magnetic Lead Switch
Protection Device
A
Residual Current Circuit Breaker (25)