4.1.2  To adjust initial settings 
 
Dealer
Select menus and determine settings according to the system available in the
household. It is recommended that all alterations of settings are done by an
authorised dealer or specialist.
• After initial installation, you may manually adjust the settings.
The initial setting remains active until the user changes it.
• The control panel can be used for multiple installations.
• Ensure the operation LED is OFF before setting.
• The system may not work properly if set wrongly. Please consult
an authorised dealer.
Press
 and
 simultaneously and hold for
5 seconds until the display shows SETTING STATUS.
Press
 or
 to select the menu.
Press
 to enter the menu.
Press
 or
 to select Yes/No, or other options.
YES: to enable the menu
No: to disable the menu
Press
 to confirm.
Control Panel
Display
Operation LED
Display
Setting
Menu (1 ~ 20)
1
Room Thermostat Connection
To select whether or not to connect to the optional room thermostat.
YES
NO
NO
NO
NO
NO
NO
2
Indoor Backup Heater Selection
To reduce the heater power if unnecessary.
*Options of kW vary depending on the model.
*3 kW / 6 kW /
9 kW
3
Water System Freeze Prevention
To activate or deactivate the water freeze prevention when the system is OFF.
YES
4
Tank Connection
To select whether or not to connect to the optional water tank unit.
Note: If NO is selected, menus 5 to 15 are skipped.
YES
5
Solar Priority
To select the use of solar panel for heating up the water tank.
YES
6
*
1,
*
2
Cooling Priority
To choose the room cooling as priority during COOL + TANK mode.
Note: If YES is selected, menus 8 and 9 are skipped for COOL + TANK mode.
YES
7
Heating Priority
To select the room heating as priority during HEAT + TANK mode.
Note: If YES is selected, menus 8 and 9 are skipped for HEAT + TANK mode.
YES
8
*
1,
*
2
Cooling/Heating Operation Interval
To set the interval for COOL or HEAT mode during COOL + TANK or HEAT +
TANK mode.
Note: If YES is selected in menus 6 and 7, this menu is skipped.
 0.5 hours  ~
10 hours
9
*
1
Tank Heat-up Interval
To set the interval for the water tank during COOL + TANK or HEAT + TANK
mode.
Note: If YES is selected in menus 6 and 7, this menu is skipped.
 5 minutes  ~
1 hour 35 minutes
 