12.8  Base Pan Heater Control (Optional) 
  To enable the base pan heater function, control panel initial setting has to be manually adjusted by activating 
Base Pan Heater menu. 
  There are 2 optional start condition can be selected, Type A or Type B. 
 Control 
details: 
1  Type A: (Default Auto Mode) 
Start conditions: 
o  When outdoor air temperature ≤ 3°C during heating and deice operation is ON. 
 
Control contents: 
o  Base pan heater is ON during deice operation and continues ON for 10 minutes after deice operation 
ends. 
 
Cancel condition: 
o  When outdoor temperature > 6°C after deice end or 
o  When operation is not at heating mode or 
o  Base pan heater ON timer count is completed. 
 
2  Type B: (ON Mode) 
Start conditions: 
o  When outdoor air temperature is ≤ 5°C and operates in heating mode, base pan heater is ON. 
 
Cancel conditions: 
o  When outdoor air temperature is > 7°C or 
o  When operation is not at heating mode. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 