1) P-Q graph for different pump HEX duty 
 
Water FlowRate. Q (L/min)
P
res
sure.
P
 (k
pa
)
P - Q
 
12.2.2  Zone Water Pump Control 
Purpose:  
  Water pump install at each zone to circulate the water inside each zone during buffer tank connection selected 
“YES” or 2 zone systems. 
 
 
 
Content: 
  AC type water pump install for this zone water pump control. When optional PCB connected, 230V output will 
drive this zone pump. 
  There are three pump can be connected through Optional PCB. (Zone 1 Pump, Zone 2 Pump, & Pool Pump) 
 
* Zone 1 pump [P1] use to circulate zone 1 water circuit & Zone 1 mixing valve [M1] adjust to control the Zone 1 
target water temperature. 
 
* Zone 2 pump [P2] use to circulate zone 2 water circuit & Zone 2 mixing valve [M2] adjust to control the Zone 2 
target water temperature. 
 
* When Pool Function select as Zone 2 circuit, [P2] use to circulate water to heat exchanger which use to transfer 
heat to pool water. 
 
* Pool pump [P3] circulates the pool water through the heat exchanger to get warm water. 
 
  Zone 1 and Zone 2 water pump start condition: 
o  Zone room request ON 
 
(eg. Zone 1 thermo ON, only zone 1 pump will turn ON) 
  Zone 1 and Zone 2 water pump stop condition: 
o  Zone room request OFF 
  Pool water pump start condition: 
o  Pool Zone request ON AND 
o  Pool function is selected 
Page of 127