WH-MXC16G9E8 - Panasonic Air Conditioner Service Manual (repair manual). Page 6

Read Panasonic WH-MXC16G9E8 Service Manual online

Item 
Unit 
Mono bloc Unit 
Input Power 
 
kW 
Cooling: 4.76 
Heating: 3.74 
Cooling: - 
Heating: 5.16 
Maximum Input Power For Mono bloc Unit 
kW 
10.27 
Power Supply 1: Phase (ø) / Max. Current (A) / Max. Input Power (W) 
Three / 15.5 / 10.27k 
Power Supply 2: Phase (ø) / Max. Current (A) / Max. Input Power (W) 
Single / 13.0 / 9.00k 
Power Supply 3: Phase (ø) / Max. Current (A) / Max. Input Power (W) 
- / - / - 
Starting Current 
7.2 
Running Current 
Cooling: 7.2 
Heating: 5.7 
Cooling: - 
Heating: 7.8 
Maximum Current For Mono bloc Unit 
15.5 
Power Factor 
Cooling: 96 
Heating: 95 
Cooling: - 
Heating: 96 
Power factor means total figure of compressor and outdoor fan motor. 
Power Cord 
Number of core 
 
 
Length 
m (ft) 
Thermostat 
 
 
Electronic Control 
Protection Device 
 
 
Electronic Control 
 
 
Item 
Unit 
Water System 
Performance Test Condition 
 
 
EN14511 
Operation Range 
Outdoor Ambient 
°C 
Cooling: 16 ~ 43 
Heating: -20 ~ 35 
 
Water Outlet 
°C 
Cooling: 5 ~ 20 
Heating: 25 ~ 55 
Internal Pressure Differential 
 
kPa 
Cooling: 40.0 
Heating: 64.0 
Water Pipe Diameter 
Inlet 
mm (inch) 
30 (1-3/16) 
 
Outlet 
mm (inch) 
30 (1-3/16) 
Water Drain Hose Inner Diameter   
mm (inch)
 
15.00 (19/32) 
Pump 
Motor Type 
 
DC Motor 
 
No. of Speed 
 
7 (software selection) 
 
Input Power 
109 
Hot Water Coil 
Type 
 
Brazed Plate 
 
No. of Plates 
 
52 
 
Size (H × W × L) 
mm 
93 × 120 × 376 
 
Water Flow Rate 
l/min (m
3
/h) 
Cooling: 35.0 (2.1) 
Heating: 45.9 (2.8) 
Pressure Relief Valve Water Circuit   
kPa 
Open: 300, Close: 265 and below 
Flow Switch 
 
 
Magnetic Lead Switch 
Protection Device 
 
Residual Current Circuit Breaker (25) 
Expansion Vessel 
Volume 
10 
 
MWP 
bar 
Capacity of Integrated Electric Heater 
kW 
9.00 
 
Note: 
1. 
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled water inlet temperature of 12°C and water outlet 
temperature of 7°C. 
2. 
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) with controlled 
water inlet temperature of 30°C and water outlet temperature of 35°C. 
3. 
Specifications are subjected to change without prior notice for further improvement. 
 
 
 
 
 
 
 
 
Page of 127
Display

Click on the first or last page to see other WH-MXC16G9E8 service manuals if exist.