Read Panasonic U-50PE2E5A / U-100PE1E8A / U-100PEY1E8 / U-125PE1E8A / U-125PEY1E8 / U-140PE1E8A / U-140PEY1E8 / S-100PU2E5B / S-125PU2E5B / S-140PU2E5B / S-71PU2E5B / S-100PF1E5B / S-125PF1E5B / S-140PF1E5B / S-71PF1E5B Service Manual online
1-1-4-20
1
1
Simultaneous (Twin) -Type
1-1. Unit Specifications
PE1
4. Low Silhouette Ducted Type S-50PF1E5B×2 / U-100PE1E8A
INDOOR
MODEL
S-50PF1E5B×2
-
-
OUTDOOR
MODEL
-
U-100PE1E8A
-
Branch pipe
MODEL
CZ-P155BK1
Performance test condition
ISO13253 / EN14511 / EN14825 / EN12102
Power supply
Ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
Capacity
kW
10.0
10.0
10.0
-
-
-
3.3
12.5
BTU/h
34100
34100
34100
-
-
-
11300
42700
Current
A
0.77×2
0.74×2
0.71×2
3.68
3.53
3.43
-
-
Input power
W
100×2
100×2
100×2
2.245k
2.245k
2.245k
-
-
TOTAL W
-
2.445k
2.445k
2.445k
840
3.700k
Annual consumption
TOTAL kWh *
4
-
-
1222.5
-
-
-
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.09
4.09 / A
4.09
3.93
3.38
Erp
*
6
Pdesign
kW
-
-
-
-
10.0
-
-
-
SEER
(W/W)
-
-
-
-
5.7
-
-
-
Annual consumption
kWh
-
-
-
-
614
-
-
-
Class
-
-
-
-
A+
-
-
-
Power factor
%
-
-
-
93
92
91
-
-
Noise indoor
dB-A (H/M/L)
34/30/26
-
-
-
-
-
Power Level dB
56/52/48
-
-
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
H
E
A
T
I
N
G
Capacity
kW
11.2
11.2
11.2
-
-
-
4.1
14.0
BTU/h
38200
38200
38200
-
-
-
14000
47800
Current
A
0.77×2
0.74×2
0.71×2
3.86
3.70
3.58
-
-
Input power
W
100×2
100×2
100×2
2.400k
2.400k
2.400k
-
-
TOTAL W
-
2.600k
2.600k
2.600k
900
4.400k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
-
-
-
4.31
4.31 / A
4.31
4.56
3.18
Erp
*
6
Pdesign at -10°C
kW
-
-
-
-
10.0
-
-
-
Tbivalent
°C
-
-
-
-
-10
-
-
-
SCOP
(W/W)
-
-
-
-
3.8
-
-
-
Annual consumption
kWh
-
-
-
-
3684
-
-
-
Class
-
-
-
-
A
-
-
-
Power factor
%
-
-
-
94
94
93
-
-
Noise indoor
dB-A (H/M/L)
34/30/26
-
-
-
Power Level dB
56/52/48
-
-
-
Noise outdoor
dB-A (H/L)
-
52/-
-
-
Power Level dB
-
69/-
-
-
EXTRA LOW TEMP Total capacity(kW) / Input power(W) / COP
-
-
Max Current(A) / Max Input power(W)
1.00×2/125×2 0.96×2/125×2 0.92×2/125×2 9.0/5.550k
9.0/5.850k
9.0/6.100k
-
Starting current(A) / Comp output(W)
-
-
-
3.86/3.0k
3.70/3.0k
3.58/3.0k
-
Network Impedance(ΩMAX.)
-
-
-
Fan motor output (Indoor/Outdoor) W
120
90x2
-
Moisture removal volume
L/h(Pt/h)
6.0
(3.0×2)
(12.6)
-
-
External static pressure
Pa
70 (MIN10 - MAX150)
-
-
Indoor
Air flow
Cooling
m³/min (ft³/min)
16.0×2/15.0×2/12.0×2 (565)×2/(530)×2/(424)×2
-
-
-
Heating
m³/min (ft³/min)
16.0×2/15.0×2/12.0×2 (565)×2/(530)×2/(424)×2
-
-
-
Outdoor
Air flow
Cooling
m³/min (ft³/min)
-
110.0
(3885)
-
-
Heating
m³/min (ft³/min)
-
95.0
(3355)
-
-
Refrigerant type / amount g(oz)
-
R410A
3.40k
(119.9)
-
Product dimension
Height mm(inch)
290 (11-13/32)
1416 (55-3/4)
-
Width
mm(inch)
800 (31-1/2)
940 (37-1/32)
-
Depth
mm(inch)
700 (27-9/16)
340 (13-13/32)
-
Packing dimension
Height mm(inch)
355
1556
-
Width
mm(inch)
1014
1055
-
Depth
mm(inch)
850
485
-
Weight
(NET)
kg(lb)
28 (62)
98 (216)
-
(GROSS) kg(lb)
35 (78)
108 (238)
-
Layers limit (actually)
9 (10)
1 (2)
-
Operation condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
-
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
-
P
I
P
I
N
G
Pipe diameter mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
-
Connecting method, Standard length m(ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
-
Pipe length range m (ft)
5 ~ 75m
(16.4 ~ 246.1)
-
Indoor unit & Outdoor unit height difference m (ft)
15m (OD located lower) / 30m (OD located higher)
(49.2/98.4)
-
Add gas amount g/m (oz/ft)
50g/m
(0.538)
-
Pipe length for additional gas m (ft)
30m
(98.4)
-
*1
: In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
: If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
: Network Impedance shall be applicable for EUROPE and CHINA models.
*4
: The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
: EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
: SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.