Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
Minimum indoor volume & floor area as against 
the amount of refrigerant is roughly as given in the 
following table.
CAUTION 
Pay special attention to any location, such as a basement, etc., where 
leaking refrigerant can accumulate, since refrigerant gas is heavier than air.
Table 1-10 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
L = Length, H = Height
Always check the gas density limit for the room in which the 
unit is installed.
WARNING 
1-12.  Check of Limit Density
When installing an air conditioner in a room, it is 
necessary to ensure that even if the refrigerant gas 
accidentally leaks out, its density does not exceed the 
limit level for that room.
If the density could exceed the limit level, it is 
necessary to provide an opening between the unit 
and the adjacent room, or to install mechanical 
ventilation which is interlocked with the leak detector.
(Total refrigerant charged amount: k
g)
(Min. indoor volume where the indoor unit is installed: m
3
)
< Limit density 0.3 (k
g/m
3
)
The limit density of refrigerant which is used in this 
unit is 0.3 k
g/m
3
 (ISO 5149).
The shipped outdoor unit comes charged with the 
amount of refrigerant fixed for each type, so add it 
to the amount that is charged in the field. (For the 
refrigerant charge amount at shipment, refer to the 
unit’s nameplate.)
40.5
54.0
27.0
13.5
0.0
20
10
0
30
40
60
70
80
90 100
50
67.5
81.0
94.5
108.0
121.5
135.0
148.5
162.0
175.5
189.0
202.5
216.0
229.5
243.0
256.0
270.0
m
2
m
3
15
10
5
0
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
283.5
297.0
310.5
324.0
337.5
k
g
Range below the 
density limit of 
0.3 k
g/m³
(Countermeasures 
not needed)
Range above the 
density limit of 0.3 
k
g/m³
(Countermeasures 
needed)
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceiling is 2.7 m high)
Items
Marks
Contents
Length (m)
Allowable tubing 
length
L1
Max. tubing 
length
Actual length
≤ 120
Equivalent length
≤ 140
ΔL (L2 – L3)
Difference between max. length and min. 
length from the No.1 distribution joint
≤ 40
1
,
2
...
n
Max. length of each distribution tube
≤ 30
1
,
2
...
n-1
+L1
Total max. tubing length including length of each 
distribution tube (only narrow tubing)
≤ 150
Allowable elevation 
difference
H1
When outdoor unit is installed higher than indoor unit
≤ 50
When outdoor unit is installed lower than indoor unit
≤ 40
H2
Max. difference between indoor units
≤ 15
TD831155-04_MINI VRF.indb   7
TD831155-04_MINI VRF.indb   7
2014/05/09   15:29:02
2014/05/09   15:29:02