7   Operation Details
7.1
Fan Mode Operation
 
Fan operation only. Fan in operation according to Remote Control or main Unit ( Touch panel) Setting.
7.1.1 Manual Setting of Fan Speed
• 
Basic Fan Speed can be manually adjusted (Lo, Hi) by using the Fan Speed Selection Button/Pad at Remote Control or
Main Unit  (Touch Control Panel).
7.2
Cooling Mode Operation
 
Cooling in operation according to Remote Control or Main Unit ( Touch Control Panel) setting.
7.2.1 Time delay Safety Control ( 3 Minute)
• 
When the compressor is stopped by Operation Switch at the Remote Control or Main Unit (Touch Control Panel), it restart
after 3 minutes when the Operation Switch at the remote Control or Main Unit  (Touch Control Panel) is turned ON.
• 
When the setting temperature is reached during cooling operation, the compresor stops and it will not startfor 3 minutes.
• 
Protection of compressor to balance the pressure in the refrigeration cycle for 3 minutes.
7.2.2 7 minutes Time Saved Control
• 
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the
compressor On temperature and OFF temperature.
7.2.3 Starting Current Control
• 
When the compressor and fan motor are simultaneously started, the fan motor will operate 1.6 second later.
7.2.4 Freeze Prevention Control
If the temperature of the indoor heat exchanger falls con-
tinuously below 1
°
C for 3 minute or more, the compres-
sor turns off to protect the heat exchanger from freezing.
The fan spee setting remains the same.
Compressor restarts when the heat exchanger tempera-
ture rises to 12
°
C (Recovery).
* 3 Minutes waiting of Time Delay Safety control is
valid for Cooling Operation.
7.2.5 Compressor Reverse Rotation Protection  Control
• 
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air
and heat exchanger is - 15
°
C for 2 minutes, compressor will stop and restart automatically ( Time Delay Safety Control
is valid).
Indoor Heat
Exchanger
Temperature
(
°
C
)
Compressor OFF
Recovery
12
1
3 min
Compressor start  for 
  5 Minutes
  -15
°
 C for 2 Minutes
Compressor
OFF
Compressor
restarts (3 minutes
waiting)
T = Intake air temperature - Indoor heat exchanger temperature.
This is to protect reverse rotation of the copressor when there is an instantaneous power failure.
- 7 -