6 Air Conditioner Performance Evaluation
6.1. Cooling.
Intake & Discharge Air
Temperature Difference
Current Drain
Determination
Remedy
     • 
• 
• 
• 
8°C and over (14.4°F)
     • 
• 
• 
• 
As specified.
     • 
• 
• 
• 
Nothing wrong.
     • 
• 
• 
• 
None.
     • 
• 
• 
• 
8°C and over (14.4°F)
     • 
• 
• 
• 
Higher than specified.
     • 
• 
• 
• 
Nothing wrong, outdoor
temperature is too high, heat
radiation is not efficient.
     • 
• 
• 
• 
Improve heat radiation.
     • 
• 
• 
• 
Under 8°C (14.4°F)
     • 
• 
• 
• 
Higher than specified.
     • 
• 
• 
• 
Something is preventing heat
radiation.
     • 
• 
• 
• 
Excessive amount of
refrigerant.
     • 
• 
• 
• 
Improve heat radiation.
     • 
• 
• 
• 
Under 8°C (14.4°F)
     • 
• 
• 
• 
Lower than specified.
     • 
• 
• 
• 
Leakage of refrigerant or
refrigerant system is blocked.
     • 
• 
• 
• 
Locate and repair leak.
     • 
• 
• 
• 
Flush refrigeration cycle.
     • 
• 
• 
• 
Under 8°C (14.4°F)
     • 
• 
• 
• 
Higher than specified by 50%.
     • 
• 
• 
• 
Compressor defect or
compressor capacitor defect.
     • 
• 
• 
• 
Replace the compressor or
compressor capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
6.2. Heating.
Intake & Discharge Air
Temperature Difference
Current Drain
Determination
Remedy
     • 
• 
• 
• 
14°C and over (25.2°F)
     • 
• 
• 
• 
As specified.
     • 
• 
• 
• 
Nothing wrong.
     • 
• 
• 
• 
None.
     • 
• 
• 
• 
14°C and over (25.2°F)
     • 
• 
• 
• 
Higher than specified.
     • 
• 
• 
• 
Nothing wrong, outdoor
temperature is high.
     • 
• 
• 
• 
Something is preventing heat
radiation at indoor heat
exchanger.
     • 
• 
• 
• 
None.
     • 
• 
• 
• 
Clean air filter.
     • 
• 
• 
• 
Under 14°C (25.2°F)
     • 
• 
• 
• 
Lower than specified.
     • 
• 
• 
• 
Nothing wrong, outdoor
temperature is low.
     • 
• 
• 
• 
Something is preventing heat
radiation at outdoor heat
exchanger.
     • 
• 
• 
• 
Leakage of refrigerant.
     • 
• 
• 
• 
Refrigerant system is blocked.
     • 
• 
• 
• 
None.
     • 
• 
• 
• 
Improve heat radiation at
outdoor heat exchanger.
     • 
• 
• 
• 
Locate and repair leak.
     • 
• 
• 
• 
Flush refrigeration cycle.
     • 
• 
• 
• 
Under 14°C (25.2°F)
     • 
• 
• 
• 
Higher than specified by 50%.
     • 
• 
• 
• 
Compressor defect.
     • 
• 
• 
• 
Compressor capacitor defect
     • 
• 
• 
• 
Replace the compressor.
     • 
• 
• 
• 
Replace the compressor
capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
7 Troubleshooting Guide
Warning: Disconnect unit from electrical power supply before making any electrical checks.
Trouble
Check
Result
Cause
Remedy
Fan Motor and
Compressor won’t run.
     • 
• 
• 
• 
Supply Voltage
     • 
• 
• 
• 
Fuse Box or Circuit
Breaker.
     • 
• 
• 
• 
Power cord or
Wiring Harness.
     • 
• 
• 
• 
Thermostat Setting.
     • 
• 
• 
• 
Less than 10% by
Rated.
     • 
• 
• 
• 
Open Contacts.
     • 
• 
• 
• 
Pulled loose or
Shorted.
     • 
• 
• 
• 
Higher than room
temp.
     • 
• 
• 
• 
Temporary or Permanent?
     • 
• 
• 
• 
Customer Restarted unit
immediately without waiting
3 minutes.
     • 
• 
• 
• 
Consult ELECTRICIAN, If
permanent.
     • 
• 
• 
• 
Repair Open Circuit.
     • 
• 
• 
• 
WAIT FOR 3 MINUTES.
     • 
• 
• 
• 
Repair or Replace it.
     • 
• 
• 
• 
Set it LOWER.
Fan Motor won’t run
(Compressor run).
     • 
• 
• 
• 
Objects around
Fan.
     • 
• 
• 
• 
RESISTANCE
between Wires.
     • 
• 
• 
• 
Capacitor Fan
Motor.
     • 
• 
• 
• 
Main Control
Switch.
     • 
• 
• 
• 
Locked Fan.
     • 
• 
• 
• 
Shorted / Open
circuit.
     • 
• 
• 
• 
OHM Meter doesn’t
Deflect.
     • 
• 
• 
• 
No contacts at
Position Shown.
     • 
• 
• 
• 
Fan Hitting Cowling or
     • 
• 
• 
• 
Foreign Materials.
     • 
• 
• 
• 
Frozen Bearings.
     • 
• 
• 
• 
Shorted or Burned out.
     • 
• 
• 
• 
Capacitor Defect.
     • 
• 
• 
• 
Main Control Switch defect.
     • 
• 
• 
• 
Adjust Fan position setting
screw.
     • 
• 
• 
• 
Remove Foreign Materials.
     • 
• 
• 
• 
Replace Fan Motor.
     • 
• 
• 
• 
Replace Fan Motor.
     • 
• 
• 
• 
Replace Capacitor Fan.
     • 
• 
• 
• 
Replace Main Control
Switch.