14.1.2 Relationship between the condition of the air conditioner and pressure and electric
current
Cooling Mode
Heating Mode
Condition of the
air conditioner
air conditioner
Low Pressure
High
Pressure
Pressure
Electric current
during
operation
during
operation
Low Pressure
High
Pressure
Pressure
Electric current
during operation
during operation
Insufficient
refrigerant
(gas leakage)
refrigerant
(gas leakage)
Ô
Ô
Ô
Ô
Ô
Ô
Clogged capillary
tube or
strainer
tube or
strainer
Ô
Ô
Ô
Ò
Ò
Ò
Short circuit in the
indoor unit
indoor unit
Ô
Ô
Ô
Ò
Ò
Ò
Heat radiation
deficiency
of the outdoor unit
deficiency
of the outdoor unit
Ò
Ò
Ò
Ô
Ô
Ô
Inefficient
compression
compression
Ò
Ô
Ô
Ò
Ô
Ô
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is
started.
started.
14.2 Breakdown Self Diagnosis Function
14.2.1 About Self Diagnosis
When the air-conditioner is stopped due to malfunction detected by itself, the operation can be restarted using AUTO
Switch on the indoor unit. In forced operation, the frequency for compressor and fan speed can not be changed and
the signal receiving sound is different.
Normal Operation ON: “pep”
Forced Operation ON: “pep”, “pep”, “pep”, “pep”
Stop: “pep”
Note: Refer to the Diagnosis Code Table for the malfunction when forced operation is not available.
Switch on the indoor unit. In forced operation, the frequency for compressor and fan speed can not be changed and
the signal receiving sound is different.
Normal Operation ON: “pep”
Forced Operation ON: “pep”, “pep”, “pep”, “pep”
Stop: “pep”
Note: Refer to the Diagnosis Code Table for the malfunction when forced operation is not available.
14.2.2 Display of Error Code
1. Keeping the CHECK button on the remote controller depressed for 5 seconds, error code ranging fromH11 to H99
can be displayed on the remote controller.
2. The error code is changed and diagnosis signal is transmitted to the indoor unit by pressing the Temp Up button on
the remote control.
3. When the malfunction of the air-conditioner matches the error code on the remote control, four beeps can be heard
from the indoor unit and the operation indicator will light up.
4. Keep the CHECK button depressed continuously for 5 seconds to cancel the diagnosis function.