13.1.4  IPM (Power transistor) Protection Control. 
1.  DC Peak Current Control 
●  When electric current to IPM exceeds set value of DC17.3 1A, the compressor will stop. It will restart after 
three minutes. 
●  If the set value is exceeded again within 30 seconds, the operation will restart after one minute. 
●  If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off. 
●  Error code [F99] will be displayed. 
2.    Overheating protection control 
When the IPM temperature rises to 112 ℃ , compressor will stop immediately. 
Compressor restarts after three minutes if the temperature decreases to 97℃ 
13.1.5 Compressor 
Overheating Prevention Control 
 
 
Instructed frequency for compressor operation will be regulated compressor discharge temperature. The change of 
frequency is as below. 
 
 
 
 
 
 
 
 
 
 
 
13.1.6  Low pressure Prevention control (Gas Leakage Detection) 
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes. 
2.  If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off. 
3. This control is not applicable for deice operation. 
 
Comp Frequency 
45 Hz or above
64 Hz or above 
58 Hz or above 
73 Hz or above 
Total Outdoor Current 
1b≤1<3 1b≤1<1.6 1b≤1<1.3 1b≤1<1.6 
Indoor Piping Temp 
20 ℃ or above 
25 ℃ or less 
20 ℃ or above 
25 ℃ or less 
Operation Mode 
Cool/Dry 
Heat 
Cool/Dry 
Heat 
Model YE9MKX 
YE12MKX 
13.1.7  Low Operation Frequency Protection Control 
If all following conditions exists, the compressor will run with the frequency of 40 Hz (YE9MKX,YE12MKX) or 30Hz 
(YE18MKX) 
Models YE9MKX, 
YE12MKX 
YE18MKX 
Intake Air Temp. 
≥30 ℃ or <15 ℃ 
------------------- 
≥30 ℃ or <14 ℃ 
≥28 ℃ or <14 ℃ 
Outdoor Temp. 
≥38 ℃ or <16 ℃ 
≥24 ℃ or <4 ℃ 
≥38 ℃ or <13 ℃ 
≥24 ℃ or <4 ℃ 
Indoor Piping Temp. 
<30 ℃ 
≥0 ℃ 
<30 ℃ 
≥0 ℃ 
Operation Mode 
Cool / Dry 
Heat 
Cool/ Dry 
Heat 
13.1.8  Compressor Tank Temperature Rise Protection Control 
a. Control start conditions 
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A. 
• During Cooling and Soft Dry operations: 
39 ℃ 
39 ℃ 
39 ℃ 
38 ℃ 
Outdoor temperature 
YE9/12MKX 
112 ℃
112 ℃ 
110 ℃ 
100 ℃ 
YE18MKX 
Page of 47