CS-XE9CKE, CU-XE9CKE, CS-XE12CKE, CU-XE12CKE - Panasonic Air Conditioner Service Manual (repair manual). Page 49

Read Panasonic CS-XE9CKE / CU-XE9CKE / CS-XE12CKE / CU-XE12CKE Service Manual online

 2. Freeze-up prevention, vacuum pump continuous running control
     • 
• 
• 
• Avoid freeze-up in tube by vacuum pump continuous running at low outdoor temp.
     • 
• 
• 
• Start condition
 a. OD temp status 1(a,b)
 b. O
2
supply level
0
     • 
• 
• 
• Control content
 a. Continuous running disregard of oxygen supply level
     • 
• 
• 
• Cancellation condition
     − 
− 
− 
− Start condition not fulfilled
     • 
• 
• 
• Exceptional condition
During deice & MOPMPS08 after deice, OD temp. status does not update as the OD fan is stop. (Air temp. detection
disable).
 3. Freeze-up prevention, 2 way valve control
     • 
• 
• 
• Open valve periodically to prevent freeze-up during low OD air temp.
     • 
• 
• 
• Open valve duration change according to air temp. status (1a or 1b).
 a. Start condition
Either one of below condition is fulfilled.
i. O
2
supply leve
0 & OD air temp status shift to 1(a,b).
49
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
Page of 110