Detail Explanation for Specification
−
−
−
− Life span counter measure
Increase life span by limiting vacuum pump continuous running period (assure life span of over 30,000h).
−
−
−
− Temp. rise counter measure.
−
−
−
− OLP
Vacuum pump OLP
i. Open temp.
: 120 ± 5°C
ii. Close temp.
: 76 ± 15°C
Data Name
Item
Data
EOPMPS05
Vacuum pump continuous running control judgement time
FF
MOPMPL01
Vacuum pump continuous running maximum supply level
2
MOPMPS06
Vacuum pump restart prevention time
30s
MOPMPS07
Vacuum pump delay start time
30s
Note: This control is deactivated when EOPMPS05 is set to FF.
3. Vacuum pump restart prevention control
•
•
•
• To avoid starting noise cause by frequent restart of vacuum pump in short period of time.
•
•
•
• If combined with other operation mode where outdoor fan running, restart control time is MOPMPS06.
•
•
•
• If Oxygen only operation, restart control time is MOPMPS06 + MOPMPS07.
•
•
•
• Restart prevention control does not operate when Oxygen is pressed ON during Oxygen delay OFF control.
4. 2 way valve control
2 way valve is ON periodically to avoid it from locking after long period of idling.
•
•
•
•
• Activation condition
When OD power relay ON signal is generated.
•
•
•
• Activation content
2 way valve is ON for about 5s (valve open).