CS-XC9CKT, CU-XC9CKT, CS-XC12CKT, CU-XC12CKT - Panasonic Air Conditioner Service Manual (repair manual). Page 19

Read Panasonic CS-XC9CKT / CU-XC9CKT / CS-XC12CKT / CU-XC12CKT Service Manual online

Time Delay Safety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Automatic Fan Speed Mode
8.3. Soft Dry Mode Operation
     • 
• 
• 
• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
     • 
• 
• 
• During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
     • 
• 
• 
• The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
     • 
• 
• 
• Once the compressor stops, it will not start for 3 minutes during Cooling operation.
     • 
• 
• 
• Same as Starting Current Control for Cooling Mode operation.
     • 
• 
• 
• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
     • 
• 
• 
• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
     • 
• 
• 
• Fan speed off and on at Lo- speed.
     • 
• 
• 
• Deodorizing Control.
19
CS-XC9CKT CU-XC9CKT / CS-XC12CKT CU-XC12CKT
Page of 78