Read Panasonic CS-XC9CKT / CU-XC9CKT / CS-XC12CKT / CU-XC12CKT Service Manual online
Time Delay Safety Control
Starting Current Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Automatic Fan Speed Mode
8.3. Soft Dry Mode Operation
•
•
•
• The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
•
•
•
• During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
•
•
•
• The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
•
•
•
• Once the compressor stops, it will not start for 3 minutes during Cooling operation.
•
•
•
• Same as Starting Current Control for Cooling Mode operation.
•
•
•
• Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
•
•
•
• Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
•
•
•
• Fan speed off and on at Lo- speed.
•
•
•
• Deodorizing Control.
19